Password For Fail-Safe Functions; Checksums - Siemens SINAMICS CU240S DP-F Operating Instructions Manual

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

Commissioning
5.5 Commissioning using the BOP
Parameter
Communication processor
P9801
P9802
P9803
r9820
P9850
P9851
P9880
P9881
P9882
P9890
P9891
P9892
r9898
P9899
5.5.6.3

Password for fail-safe functions

Description
There are three parameters associated with the password protection system. They require
level 3 access (only important when using OP) – the parameters are as follows:
● P9761 to get access to the fail-safe paramters
● P9762 and P9763 to change the currently valid password
Details see "General Steps for Commissioning Fail-Safe Functions"
5.5.6.4

Checksums

Description
All parameters for fail-safe functions are verified by the use of checksums. These checksums
ensure the integrity of the data held within the drive processors memory.
There are four checksum, two for each of the processors, these are:
● r9798 – actual checksum for P1.
● P9799 – reference checksum for P1.
● r9898 – actual checksum for P2.
● P9899 – reference checksum for P2.
82
Description
SI enable parameter
SI enable safe brake monitoring
SI Selection of safety command source
SI Status word
SI Safe Digital Input debounce delay time
SI Safe Digital Input filter delay time
SI braking ramp delay
SI braking ramp down time
SI minimum speed for standstill detection
SI setpoint for SLS
SI tolerance for SLS
SI response to selecting SLS
SI display checksum
SI parameter checksum
Unit
-
-
-
-
s
s
s
s
kHz
kHz
kHz
-
-
-
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Default
Min.
Max.
value
value
value
2
0
2
0
0
1
0
0
240
-
-
-
0.050
0.000
2.000
0.005
0.000
0.100
0.250
0.010
99.000
10.000 0.100
99.000
0.005
0.002
0.020
0.010
0.001
0.300
0.013
0.005
0.302
1
0
2
0000h
0000h
FFFFh
0000h
0000h
FFFFh
Control Units CU240S