Vector Control mode
For applications using Vector Control (P1300 = 20 ... 23), quick commissioning should be
performed as described in the following table:
Parameters designated with an "*" offer more settings than are actually shown here. Refer to
the Parameter list for additional settings.
Table 5-7
Quick commissioning - Vector Control mode
Parameter
Description
P0003 = 3
User access level*
1: Standard: Allows access into most frequently used parameters (default)
2: Extended: Allows extended access e.g. to inverter I/O functions
3: Expert: For expert use only
P0004 = 0
Parameter filter*
0: All parameters (default)
2: Inverter
3: Motor
4: Speed sensor
P0010 = 1
Commissioning parameter filter*
0: Ready (default)
1: Quick commissioning
30: Factory setting
Note: P0010 should be set to 1 in order to parameterize the data of the motor rating plate.
P0100 = 0
Europe/North America (enter the motor frequency)
0: Europe [kW], frequency default, 50 Hz (default)
1: North America [hp]. frequency default, 60 Hz
2: North America [kW], frequency default, 60 Hz
P0304 = ...
Rated motor voltage (enter value from the motor rating plate in volts)
The input of rating plate data must correspond with the wiring of the motor (star/delta). This
means, if delta wiring is used for the motor, delta rating plate data has to be entered.
P0305 = ...
Rated motor current
enter value from the motor rating plate in ampere
P0307 = ...
Rated motor power
enter value from the motor rating plate in kW or hp
Note: if P0100 = 0 or 2, data is in kW and if P0100 = 1, data is in hp.
P0310 = ...
Rated motor frequency
enter value from the motor rating plate in Hz
Pole pair number recalculated automatically if parameter is changed.
P0311 = ...
Rated motor speed
enter value from the motor rating plate in RPM)
Setting P0311 = 0 causes internal calculation of value.
Note: Required for vector control and V/f control with speed controller.
Slip compensation in V/f control requires rated motor speed for correct operation.
P0700 = 2
Selection of command source*
0: Factory default setting
1: BOP (keypad)
2: Terminal (Default for CU240S)
4: USS on RS232
5: USS on RS485
6: Fieldbus (Default for DP and PN variants)
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Commissioning
5.5 Commissioning using the BOP
Setting
61