Note
If P0014 = 0, you can always transfer all parameter values from RAM into EEPROM via
P0971. The duration of the data transfer depends on the number of changed parameters.
The data transfer can last up to 3 minutes. During the data transfer, BOP displays "bUSY".
Automatic Download
The Automatic Download at start-up is controlled via P8458. With the Automatic Download
all necessary parameters including the parameters regarding fail-safe functions are
downloaded into the inverter.
Note
MMC for "Automatic Download"
For an Automatic Download always the file clone00.bin will be used.
The user has to take care, that clone00.bin (saved as "clone00.bin" with STARTER on PC or
via setting P0804 = 00 with the BOP) is available on the MMC, used for an automatic
parameter download at start-up. Otherwise Automatic Download will not be processed.
Parameter P8458 controls the kind auf the Automatic Download. The possible settings for
P8458 and their functions are given below.
P8458 = 0: Automatic parameter download from the MMC is inhibited.
P8458 = 1: Automatic parameter download from the MMC only once (at the next start-up
P8458 = 2: Automatic parameter download from the MMC after each start-up of the
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
of the CU (default setting)). After the download P8458 is set to 0.
control unit.
Commissioning
5.7 Commissioning with the MMC
101