Siemens SINAMICS CU240S DP-F Operating Instructions Manual page 149

Hide thumbs Also See for SINAMICS CU240S DP-F:
Table of Contents

Advertisement

Table 6-26
DIP switch
Add to address
Example 1: Address = 3 = 1 + 2
Example 2: Address = 88 = 8 + 16 + 64
The valid address range is shown in the table below:
Table 6-27
DIP switch
settings
0
1 ... 126
Note
Address 126 cannot be used with a SIMATIC plc.
PROFIBUS DP parameters
The following parameters must be set to start-up the PROFIBUS DP interface:
Table 6-28
Parameter
P0918
P0700
P0922
P1000
P2038
P2042
r2050
P2051
P2041
P2040
P0927
r2054
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Example address for the PROFIBUS DP interface
PROFIBUS DP address
Meaning
PROFIBUS DP address is determined by P0918
PROFIBUS DP address range
PROFIBUS DP parameters
Content
PROFIBUS address
Selection of command source
Selection of PROFIBUS standard telegram
Selection of frequency setpoint
Selection of communication profile
Selection of the ident number (native or NAMUR) send to PLC
Process data setpoint source (BICO)
Process data actual values (BICO)
Communication board functions
Process data telegram failure time
Modification source for parameters
Communication board diagnostics
6.4 Communication via PROFIBUS
1
2
3
4
1
2
4
8
Communication
5
6
7
16
32
64
149