Commissioning
5.5 Commissioning using the BOP
JOG frequency
Parameter
Description
P1057 = 1
JOG Enable
P1057 = 0 JOG-function disabled
P1057 = 1 JOG-function enabled (default)
P1058 = 5
JOG frequency right
Frequency in Hz when the motor is being jogged in the clockwise direction.
P1059 = 5
JOG frequency left
Frequency in Hz when the motor is being jogged in the counter-clockwise direction.
P1060 = 45
JOG ramp-up time
Ramp-up time in seconds from 0 to the
maximum frequency (P1082). The JOG ramp-up
is limited by P1058 or P1059.
P1061 = 50
JOG ramp-down time
Ramp-down time in seconds from the maximum
frequency (P1082) to 0.
Additional Setpoints
Parameter
Description
P1074 = 1.0
BI: disable additional setpoint
P1075 = 775
CI: additional setpoint
Defines the source of the additional setpoint which is added to the main setpoint.
Common settings:
755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint
P1076 = 1.0
CI: additional setpoint scaling
Defines the source to scale the additional setpoint.
Common settings:
1: Scaling of 1.0 (100 %)755: Analog input setpoint
1024: Fixed frequency setpoint
1050: MOP setpoint
74
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Setting
Setting
Control Units CU240S