Sensor loops overview and wiring (B921C/B942/B942W only)

The keypad detects three states (Open, Supervised, Short) on its sensor loops and sends the
conditions to the control panel. Each sensor loop has an assigned point number.
Use twisted-pair wire for the module sensor loops to avoid electromagnetic interference
problems. Run wires away from the premises telephone and AC wiring.
To wire detection devices to keypad inputs, connect them to the keypad terminals labeled for
COM, and 1, 2, 3, or 4. Wire resistance on each sensor loop must be less than 100 Ω with the
detection devices connected. The terminal strip supports 12 to 22 AWG (0.65 to 2 mm) wires.
Figure 9.1: Keypad inputs wiring (B921C shown)
Callout ᅳ Description
1 ᅳ Keypad terminal strip
2 ᅳ Sensor loop
3 ᅳ 1 kΩ EOL resistor (P/N: F01U026703)
Bosch Security Systems, Inc.
1
SDI2
ON-BOARD POINTS
Device Bus
Voltage Ranges
R Y G B
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
1 k
End of Line Resistors
AUX
1 COM 2
3 COM 4 5 COM 6
- 12 V +
COM AUX
R
Y
G
B
1
COM
2
3
COM
4
5
COM
PWR A
B COM
R
Y
G
B
1 Control panel
2 Keypad
3 Terminal strip wiring
1COM2 3COM4
Keypads, keyswitches, keyfobs and transmitters | en
C
OUTPUT
B
7 COM 8
6
7
COM
8
Installation Manual
45
2
2018.07 | 16 | F.01U.287.180

Advertisement

Table of Contents
loading

This manual is also suitable for:

B5512B4512B4512eB3512eB3512B5512e

Table of Contents