3.10 Loop 1 Control Parameters Set Up Group

Function
Prompt
Lower Display
PV SOURC
Process Variable Source
Tuning Parameter Sets
PID SETS
Automatic Switchover
SW VALUE
Value
LSP'S
Local Setpoint Source
Remote Setpoint Source
RSP SRC
Automatic Bias
AUTOBIAS
Local Setpoint Tracking
SP TRACK
Power Up Mode Recall
PWR MODE
TPSC Output Start-up
PWR OUT
Mode
Setpoint High Limit
SP HiLIM
SP LoLIM
Setpoint Low Limit
Control Output Direction
ACTION
Output Change Rate
OUT RATE
Output Rate Up Value
PCT/M UP
12/00

Table 3-9 Control Group Function Prompts

Function
Name
UDC3300 Basic Model: DC33XB User Manual
Selections or
Range of Setting
Upper Display
INP 1
IN AL1
INP 2
1 ONLY
2KEYBD
2PV SW
2SP SW
Value in engineering units within
PV or SP range limits
1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
NONE
IN AL1
INP 2
ENABLE
DISABL
NONE
PV
RSP
MANUAL
A LSP
A RSP
AM SP
AM LSP
LAST
F'SAFE
0 to 100% of span input in
engineering units
0 to 100% of span input in
engineering units
DIRECT
REVRSE
ENABLE
DISABL
Does not apply to 3 Position Step
Control algorithm.
0 to 9999% per minute
Configuration
Factory
Setting
INP 1
1 ONLY
0.00
1 ONLY
NONE
DISABL
NONE
MANUAL
LAST
1000
0
REVRSE
DISABL
0
31