Loop 1 Control Parameters Set Up Group; Table 3-9 Control Group Function Prompts - Honeywell UDC3300 User Manual

Universal digital controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

3.10 Loop 1 Control Parameters Set Up Group

Function
Prompt
Lower Display
Process Variable Source
PV SOURC
Tuning Parameter Sets
PID SETS
SW VALUE
Automatic Switchover
Value
Local Setpoint Source
LSP'S
Remote Setpoint Source
RSP SRC
Automatic Bias
AUTOBIAS
SP TRACK
Local Setpoint Tracking
Power Up Mode Recall
PWR MODE
TPSC Output Start-up
PWR OUT
Mode
SP HiLIM
Setpoint High Limit
Setpoint Low Limit
SP LoLIM
Control Output Direction
ACTION
Output Change Rate
OUT RATE
PCT/M UP
Output Rate Up Value
5/00

Table 3-9 Control Group Function Prompts

Function
Name
UDC3300 Basic Model: DC330B User Manual
Selections or
Range of Setting
Upper Display
INP 1
IN AL1
INP 2
1 ONLY
2KEYBD
2PV SW
2SP SW
Value in engineering units within
PV or SP range limits
1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
NONE
IN AL1
INP 2
ENABLE
DISABL
NONE
PV
RSP
MANUAL
A LSP
A RSP
AM SP
AM LSP
LAST
F'SAFE
0 to 100% of span input in
engineering units
0 to 100% of span input in
engineering units
DIRECT
REVRSE
ENABLE
DISABL
Does not apply to 3 Position Step
Control algorithm.
0 to 9999% per minute
Configuration
Factory
Setting
INP 1
1 ONLY
0.00
1 ONLY
NONE
DISABL
NONE
MANUAL
LAST
1000
0
REVRSE
DISABL
0
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dc3300

Table of Contents