Sun Fire V60X Server Fan Module Replacement - Sun Microsystems Sun Fire V60x Manual

Table of Contents

Advertisement

5.5.9.2

Sun Fire V60x Server Fan Module Replacement

Replacing the fan module is essentially the reverse of the procedure described in
"Sun Fire V60x Server Fan Module Removal" on page 5-41.
1. Remove the air baffle.
2. Remove the processor air duct.
3. Position the new fan module so that the fan cable is located closest to the center of
the chassis.
4. Slide the "L" shaped foot on the chassis sidewall end of the fan module under the
chassis tab.
5. Lower the module onto the chassis floor and slide it as far to the right as it will
go.
6. Ensure that the fan module is situated between the raised guides, not on top of
them.
7. Press down on the left end of the module and press in on the release tab until the
tab snaps into the chassis slot.
8. Plug the fan module power cable into the system fan connector on the server
board.
9. Install the air baffle.
10. Replace the processor air duct.
11. Replace the chassis cover.
Note – The Comprehensive Test should be run after changing any FRU, CRU, or
adding an optional component. See "Run Platform Confidence Test (PCT)" on
page 4-31.
Chapter 5 Maintaining the Server
5-43