Input Current Control - Daikin Floor Standing Type F-Series Service Manual

Inverter pair
Table of Contents

Advertisement

Control Specification
3.5

Input Current Control

Outline
The microcomputer calculates the input current during the compressor is running, and sets the
frequency upper limit from the input current.
In case of heat pump model, this control which is the upper limit control of the frequency takes
priority to the lower limit of control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
Drooping zone
Keep zone
Reset zone
Limitation of current drooping and stop value according to the outdoor temperature
49
After 2.5 seconds in this zone, the compressor is stopped.
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is pulled down by 2 Hz every second until it reaches the keep
zone.
The present maximum frequency goes on.
Limit of the frequency is canceled.
Cooling
(A)
(A)
Normal mode
ECONO mode
(A)
Normal mode
ECONO mode
Cooling
(A)
(A)
Normal mode
ECONO mode
(A)
Normal mode
ECONO mode
The current droops when outdoor temperature becomes higher than a certain level
(depending on the model).
Compressor Stop
RK(X)S25F2V1B
RK(X)S25G2V1B
Heating
Cooling
9.25
6.0
7.5
6.5
3.25
5.25
6.75
5.75
2.5
RK(X)S35F2V1B
RK(X)S35G2V1B9
RK(X)S35G2V1B
Heating
Cooling
9.25
7.25
8.25
3.25
6.5
7.5
2.5
SiBE06-708_A
Stop Zone
Drooping Zone
Keep Zone
Reset Zone
(R4304)
RK(X)S25G2V1B9
Heating
Cooling
9.25
9.25
7.5
6.25
3.25
3.25
6.75
5.5
2.5
2.5
RK(X)S50F2V1B
RK(X)S50G2V1B
Heating
Cooling
9.25
20.0
8.25
10.0
3.25
7.0
7.5
9.0
2.5
6.0
Function and Control
Heating
7.5
6.75
Heating
15.0
10.5
14.0
9.5