Discharge Pipe Temperature Control; Input Current Control - Daikin SUPER MULTI NX G Series Service Manual

Table of Contents

Advertisement

Control Specification
3.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
this temperature from going up further.
Detail
3.5

Input Current Control

Outline
An input current is detected by the CT when the compressor is running, and the frequency upper
limit is set from the input current.
In case of heat pump model, this control, which is the upper limit control of the frequency, takes
priority over the lower limit control of four-way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
 After 2.5 seconds in this zone, the compressor is stopped.
Dropping zone
 The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
 After this, the output frequency is pulled down by 2 Hz every second until it reaches the keep
Keep zone
 The present maximum frequency goes on.
Reset zone
 Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
 The current drops when outdoor temperature becomes higher than a certain level (depending
49
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping
zone
The timer starts, and the frequency is
Keep zone
The upper limit of frequency is kept.
Reset zone
The upper limit of frequency is canceled.
zone.
on the model).
Dropping zone
Keep zone
Reset zone
Compressor Stop
SiUS12-928_A
120°C(248°F)
111°C(232°F)
109°C(228°F)
107°C(225°F)
(R10701)
Control
dropping
.
Stop Zone
Dropping Zone
Keep Zone
Reset Zone
(R11682)
Function and Control

Advertisement

Table of Contents
loading

Table of Contents