NTI SERVER ENVIRONMENT MONITORING SYSTEM
Sensor connected to
Sensor is rated for more current than
DIGITAL IN terminal
terminal can supply. Fuse protecting
stops working
port has opened.
ENVIROMUX-EDR-SF and
ENVIROMUX-EDR-SCR Electric
Strike may cause this if connected to
DIGITAL IN terminals 1-7
RECYCLING INFORMATION
Attention: Residents of New York, USA
This product is subject to New York's recycle laws regarding lead acid batteries.
WARNING
This unit contains a sealed lead acid battery. Battery maintenance must be performed by an authorized trained
technician.
Always follow local laws and regulations regarding the disposal of this unit.
For instruction on the proper disposal of the battery contained in this unit, either contact the Rechargeable Battery Recycling
Corporation (RBRC) at 800-822-8837 or go to their website at
For instruction on the safe removal and disposal of the battery, visit the ENVIROMUX-SEMS-16 website at
http://www.networktechinc.com/enviro-rems.html
In order to return the ENVIROMUX-SEMS-16 to Network Technologies Inc, please contact us at (800) 742-8324 (800-RGB-
TECH) or (330) 562-7070 to receive a return goods authorization.
responsibility of the customer.
Pb
www.call2recycle.org.
or contact us at (800) 742-8324 (800-RGB-TECH) or (330) 562-7070 .
79
Disconnect failed sensor. After approx. 10 minutes
internal fuse should reset. Reconnect sensor to terminals
provided sensor current requirements fall within terminal
limitations.
DIGITAL IN terminals 1-7 max. load = 50mA
DIGITAL IN terminal 8 max. load = 650mA