NTI SERVER ENVIRONMENT MONITORING SYSTEM

SENSOR SPECIFICATIONS

Internal Temperature Sensor

Temperature Range.......................................32° to 104° F (0° to 40° C)
Temperature Accuracy...................................+/- 2° F (+/- 1° C)

Internal Humidity Sensor

Humidity Range .............................................20% to 80% RH at temperatures between 0° to 40° C
Humidity Accuracy .........................................+/- 5 % RH

Internal Power Sensor

Measurable Mains Voltage ............................0 – 255VAC
Low Battery Voltage.......................................10.7V

External Temperature Sensor

NTI Model #.................................................... ENVIROMUX-STS
Connector ......................................................RJ45 connector
Temperature Range.......................................32° to 122° F (0° to 50° C)
Temperature Accuracy...................................+/- 2° F (+/- 1° C)
Voltage Supply...............................................5V DC
Current Consumption.....................................20mA
Max. Cable Length.........................................1000 ft
Communication Type .....................................RS485
Data rate ........................................................96kbps

External Humidity Sensor

NTI Model #.................................................... ENVIROMUX-SHS
Connector ......................................................RJ45 connector
Humidity Range .............................................20% to 80% RH at temperatures between 0° to 40° C
Humidity Accuracy .........................................+/- 5 % RH
Voltage Supply...............................................5V DC
Current Consumption.....................................20mA
Max. Cable Length.........................................1000 ft
Communication Type .....................................RS485
Data rate ........................................................96kbps

External Temperature and Humidity Sensor

NTI Model #.................................................... ENVIROMUX-STHS
Connector ......................................................RJ45 connector
Temperature Range.......................................32° to 122° F (0° to 50° C)
Temperature Accuracy...................................+/- 2° F (+/- 1° C)
Humidity Range .............................................20% to 80% RH at temperatures between 0° to 50° C
Humidity Accuracy .........................................+/- 5 % RH
Voltage Supply...............................................5V DC
Current Consumption.....................................20mA
Max. Cable Length.........................................1000 ft
Communication Type .....................................RS485
Data rate ........................................................96kbps