Figure 22- Power Supply Alerts Configuration - Network Technologies ENVIROMUX-SEMS-16 Installation And Operation Manual

Enviromux series server environment monitoring system
Hide thumbs Also See for ENVIROMUX-SEMS-16:
Table of Contents

Advertisement

NTI SERVER ENVIRONMENT MONITORING SYSTEM

Figure 22- Power Supply alerts configuration

Alert Settings
Notify when return to normal: The user can also be notified when the power supply has returned to the normal operation by
selecting the "Notify when return to normal" box.
Notify Again: Specifies the amount of time before an alert message is repeated.
The repeated alert can be set to occur from 1-
999 seconds, minutes, or hours.
Automatically acknowledge alert when condition clears: The sensor can be configured to automatically acknowledge the alert
and return the status to normal in the event the alert condition clears and normal operation resumes.
Alert Notifications
The alert can be configured to notify one or more users via email, SNMP traps (V1), Syslog messages, or SMS alerts. It can
also activate an audible siren, or an alarm beacon.
Alerts are also indicated on the "Int Alert" or "Ext Alert " LEDs on the front of
the ENVIROMUX and in the WEB interface.
Outputs
Each power supply can be associated with one of the connections labeled "Output Relays" (see page 33), and that connection
can be set to open or close the contacts of the relay either on alert, or when returning to normal.
The tamper can also block the
output command generated by the alert. In this way other devices can be controlled by power supply alerts.
Examples of this
can be found in the wiring examples on pages 73 and 74.
24