NTI SERVER ENVIRONMENT MONITORING SYSTEM
FEATURES AND FUNCTIONS
NTI
ENVIROMUX
TM
R
AREA ALERT
TM
Netwo rk Te chnologie s Inc
14
NTI
R
NETWORK TECHNOLOGIES INC
1275 Danner Dr, Aurora, OH 44202
2
3
1. LEDs- Pwr- indicates when power to ENVIROMUX is ON (solid ON) and when power failure has occurred (battery power is
ON- LED is blinking once per second)
Low Batt- indicates that the backup battery is running low on power, disconnected, or in failure
Check Log- illuminates when a new entry that is not an alert is added to the log
Int Alert- illuminates when an internal sensor generates an alert
Ext Alert- illuminates when an external sensor generates an alert
See LED Status Chart (page 64) for more on LED indicators.
2. IEC Connector- for connecting the IEC power cable (see also "Dual Power Option" on page 15)
3. Power Switch- used to turn the power to the ENVIROMUX ON/OFF
4. RJ45 Sensors- RJ45 female connectors- for attachment of various sensors
5. Digital IN- connection block for wired sensors (2-to-4 wire)
6. Output Relays- connection block for devices to be controlled in the event of alerts
7. In and Out- ports for expansion to up to 4 connected systems
8. Console-DB9 female connector- DCE port for RS232 serial connection of a terminal to control the system
9. Ethernet- RJ45 female connector- for connection to a Local Area Network (LAN) for remote configuration, monitoring, and
control
10. Aux Pwr- terminal block for powering a GSM modem with 12VDC power at 150mA max. (fuse protected)
11 .Aux- DB9 male connector- DTE port for serial connection of a GSM modem for cell phone monitoring of alerts
12. Siren- terminal block for two-wire connections of audible alarm (ENVIROMUX-SRN-M Siren on page 11)
13. Beacon- terminal block for two-wire connection of visual alarm (ENVIROMUX-BCN-R Beacon on page 11)
14. Ground post- for external bonding connection
15. Reset Button- for rebooting the firmware for the ENVIROMUX-SEMS (see page 64 for details)
FRONT VIEW OF ENVIROMUX-SEMS-16
Low
Pwr
Batt
15
REAR VIEW OF ENVIROMUX-SEMS-16
RJ45 SENSORS
1
+ 12V + 12V + 12V
Tel:330-562-7070
www.networktechinc.com
4
Check
Int
Ext
Log
Alert
Alert
1
13
DIGITAL IN
BEACON
2
3
4
5
6
7
8
+12V
+ 12V
+ 12V + 12V
+ 12V + 12V
OUTPUT RELAYS
1
2
3
5
6
7
12
11
10
AUX
SIREN
AUX PWR
+12V
+12V
OUT
CONSOLE
4
IN
ETHERNET
7
8
9
Need help?
Do you have a question about the ENVIROMUX-SEMS-16 and is the answer not in the manual?