Figure 25- Extra Fields On Current Sensor Configuration Page - Network Technologies ENVIROMUX-SEMS-16 Installation And Operation Manual

Enviromux series server environment monitoring system
Hide thumbs Also See for ENVIROMUX-SEMS-16:
Table of Contents

Advertisement

NTI SERVER ENVIRONMENT MONITORING SYSTEM

Figure 25- Extra fields on Current Sensor Configuration page

Thresholds
Minimum Threshold: The user must define the lowest acceptable value for the sensors. If the sensor measures a value below
this threshold, the sensor will move to alert status. The assigned value should be within the range defined by Minimum Level and
Maximum Level and lower than the assigned Maximum Threshold value. If values out of the range are entered, they will be
automatically adjusted to be within range.
Maximum Threshold: The user must define the highest acceptable value for the sensors. If the sensor measures a value above
this threshold, the sensor will move to alert status. The assigned value should be within the range defined by Minimum Level and
Maximum Level and higher than the assigned Minimum Threshold value. If values out of the range are entered, they will be
automatically adjusted to be within range.
Sampling
Sampling Period: Determines how often the displayed sensor value is refreshed on the Sensor page. A numeric value and a
measurement unit (minimum 1 seconds, maximum 999 minutes) should be entered.
Note: Regardless of the sampling period ENVIROMUX will read the sensor every second and will send an alert as
needed based on the configured values. An extended sampling period will not delay an alert response from ENVIROMUX.
The shorter the sampling period, the more traffic that will be seen on the network.
Add Data to Log File: This is a check-box that lets the user decide if the data sampled should be recorded in the Data Log.
Add reading to log file every: Enter the time period between logged measurements.
28