INSTALLATION

Hardwired UPS Installation

Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to
your equipment and void your warranty.
The Powerware 9140 hardwired models require a dedicated branch
circuit that meets the following requirements:
S
S
S
S
S
To hardwire the UPS:
1.
2.
46
EATON Powerware
For single-phase: 60A (10 kVA models) or 50A (7.5 kVA models) circuit
with short circuit and overcurrent protection
For three-phase: 30A (10 kVA models) or 20A (7.5 kVA models) circuit
with short circuit and overcurrent protection. A separate single-phase
input must have a 60A (10 kVA models) or 50A (7.5 kVA models)
breaker connected to the bypass input.
200–240 Vac
50/60 Hz
The breaker must be wall-mounted and be readily accessible to the
operator
Flexible metal conduit (recommended for ease of service and
maintenance)
Verify that all circuit breakers are in the OFF (O) position.
If you are installing power management software, connect your
computer to the USB port, UPS communication port, or optional
X-Slot card (see page 69). For the communication port, use the
supplied serial cable.
®
9140 UPS (7.5–10 kVA) User's Guide