Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
— causing hours of lost productivity and expensive repairs. With the Powerware 9140, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Powerware 9140 UPS with an optional Extended Battery Module (EBM).
Page 10
INTRODUCTION Providing outstanding performance and reliability, the Powerware 9140’s unique benefits include the following: Online, double-conversion, high-frequency UPS design with pure sine wave output and power-factor correction. The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery.
UPS and the total equipment connected to the output of this UPS must not have an earth leakage current greater than 3.5 milliamperes. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 12
I overensstemmelse med internationale normer og bestemmelser for el-installation må det udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 3,5 milliampere. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%). Voor UPS systemen met vast-bedrade uitgangen, moet de overstroombeveiliging voor wisselstroom uitvoercircuit(s) door anderen worden geleverd. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 14
Houd onbevoegden uit de buurt van de accu’s. De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke voorschriften. Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 15
Älä päästä valtuuttamatonta henkilöstöä lähelle akkuja. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 16
Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de fuite à la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 3,5 mA. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 17
Die USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben. Für USV-Systeme mit festverdrahteten Eingängen muß der Überstromschutz für die Ausgangswechselstromkreise anderweitig bereitgestellt werden. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 18
Vorsichtsmaßnahmen verfügt. Nicht autorisiertes Personal von Batterien fern halten. Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. Batterien niemals verbrennen, da sie explodieren können. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una corrente di dispersione di terra superiore a 3,5 milliampere. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 20
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare riferimento alle disposizioni locali. Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 22
Para estar de acordo com os padrões internacionais e os regulamentos de fiação, o equipamento total conectado à saída desta UPS não deve ter uma corrente de fuga à terra maior que 3,5 miliampères. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 23
В данном ИБП имеются СМЕРТЕЛЬНО ОПАСНЫЕ НАПРЯЖЕНИЯ. Все работы по ремонту и обслуживанию должны выполняться ТОЛЬКО УПОЛНОМОЧЕННЫМ ОБСЛУЖИВАЮЩИМ ПЕРСОНАЛОМ. Внутри ИБП нет узлов, ОБСЛУЖИВАЕМЫХ ПОЛЬЗОВАТЕЛЕМ. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 24
Необходимо соблюдать правила утилизации аккумуляторов. Обратитесь к местным нормативным актам за информацией о требованиях к утилизации. Никогда не бросайте аккумуляторы в огонь. Аккумуляторы могут взорваться под воздействием огня. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes. Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 26
Håll ej behörig personal borta från batterierna. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
NOTE Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
UPS directly above the EBM(s). If installing optional EBM(s), continue to the following section, “EBM Setup.” Otherwise, continue to “UPS Setup” on page 30. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
INSTALLATION EBM Setup The Powerware 9140 EBM comes with all hardware required for installation in a standard EIA or JIS seismic rack-mount configuration with square or round mounting holes. The rail assemblies adjust to mount in 19-inch panel racks from 24 to 30 inches deep.
Position 4 Mounting Bracket Position 3 Position 2 Bottom of Rack or Top of Other Cabinet Figure 2. Front Rail Screw Positions for the EBM ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 31
Adjust the rail size on the rail assembly for the depth of your rack (see Figure 4). Rear Front Figure 4. Adjusting the Rail Depth (Right Rail Assembly Shown) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 32
7 mm (9/32”) nut driver. See Figure 6. Repeat for the other rail. M4 Screws M4 Locknuts Figure 6. Tightening the Rail Adjustment (Right Rail Assembly Shown) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 33
EBM and secure with four supplied M4 flat-head screws. Rear Mounting Brackets (2) Front Mounting Brackets (2) Figure 7. Installing the EBM Front and Rear Mounting Brackets ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 34
Position 8 (M6 screw and clip/cage nut) Position 3 (M5 screw) Position 2 (M5 screw) Figure 9. Securing the Front of the EBM ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 35
EBM to the rack using four M6 machine screws as shown in Figure 10. Tighten the wing bolts on the seismic mounting brackets. M6 Screws Figure 10. Securing the Optional EBM Seismic Mounting Brackets ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Battery Tray Lock Figure 12. Installing the Battery Trays ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 37
INSTALLATION Replace the EBM front cover and tighten the two front cover screws (see Figure 13). Figure 13. Replacing the EBM Front Cover ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
INSTALLATION UPS Setup The Powerware 9140 UPS comes with all hardware required for installation in a standard EIA or JIS seismic rack-mount configuration with square and round mounting holes. The rail assemblies adjust to mount in 19-inch panel racks from 24 to 30 inches deep.
Lower Front Mounting Position 3 Bracket Position 2 Bottom of Rack or Top of Other Cabinet Figure 14. Front Rail Screw Positions for the UPS ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 40
Adjust the rail size on the rail assembly for the depth of your rack (see Figure 16). Rear Front Figure 16. Adjusting the Rail Depth (Right Rail Assembly Shown) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 41
7 mm (9/32”) nut driver. See Figure 18. Repeat for the other rail. M4 Screws M4 Locknuts Figure 18. Tightening the Rail Adjustment (Right Rail Assembly Shown) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 42
Use two hands to support the module. Figure 19. Removing the UPS Front Cover and Electronics Module ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 43
UPS and secure with four supplied M4 flat-head screws. Rear Mounting Brackets (2) Front Mounting Brackets (4) Figure 20. Installing the UPS Front and Rear Mounting Brackets ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 44
See Figure 21. Do not tighten the wing bolts. Figure 21. Installing the Optional UPS Seismic Mounting Brackets ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 45
(M6 screw cage/clip Position 11 nut) Position 8 Position 3 (M5 screw) Position 2 (M5 screw) Optional Figure 22. Securing the Front of the UPS ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 46
16. Replace the electronics module by sliding it carefully into the cabinet. Verify that it seats against the rear of the cabinet. Turn the module lock switch to the LOCK position. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Figure 25. Replacing the UPS Front Cover If you are installing an optional EBM, continue to the following section, “EBM Installation.” Otherwise, continue to “UPS Installation” on page 42. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Continue to the following section, “UPS Installation.” NOTE After UPS installation, ensure maximum battery runtime by configuring the UPS for the correct number of EBMs (see page 67). ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty. The Powerware 9140 plug-receptacle models require a dedicated branch circuit that meets the following requirements: 60A (10 kVA models) or 50A (7.5 kVA models) circuit with short circuit and overcurrent protection 200–240 Vac...
Page 51
UPS is in Standby mode with the equipment offline. The fans run and the LCD illuminates and displays the UPS startup screens. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 52
(4) C19 Output Receptacles Ground X-Slot Connector Bonding Communication Screw IEC 309-60A IEC 309-60A Input Power Cord Output Power Cord Figure 27. Plug-Receptacle UPS Rear Panel ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 53
NOTE The batteries charge to 80% capacity in less than 5 hours. However, it is recommended that the batteries charge for 48 hours after installation or long-term storage. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty. The Powerware 9140 hardwired models require a dedicated branch circuit that meets the following requirements: For single-phase: 60A (10 kVA models) or 50A (7.5 kVA models) circuit with short circuit and overcurrent protection For three-phase: 30A (10 kVA models) or 20A (7.5 kVA models) circuit...
Page 56
NOTE Install no more than one wire per terminal. Figure 29. Single Input Feed (Single-Phase) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 57
NOTE Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors. Figure 31. Dual Input Feed (Three-Phase) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 58
(200, 220-240V), utility neutral connects to UPS neutral. The ground screw on the input terminal block can be used for input ground if an appropriate ring lug is available. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 59
Input Bypass Ground * Use 13.3 mm (6 AWG) 90_C copper wire minimum. For ease of installation, use appropriately sized ferrules on the end of each wire. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 60
NOTE Resetting the phase input selector switch while the UPS is running has no effect on UPS operation. The UPS reads the position of the switch only when powering on. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 61
The fans run and the LCD illuminates and displays the UPS startup screens. 20. To change the factory-set defaults, see “User Settings” on page 60. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
48 hours after installation or long-term storage. REPO and ROO Installation The Powerware 9140 includes a two-position terminal (see Figure 35) that can be either left open or configured one of two ways: As a remote emergency power-off (REPO) contact that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location.
Page 63
Refer to the following table to plan the REPO or ROO behavior: REPO Contact Open Contact Closed Shutdown Online Online Shutdown Contact Open Contact Closed Online Standby Standby Online ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 64
10. Activate the external REPO or ROO switch to test the function. Verify the status change on the UPS display. 11. REPO only. De-activate the external REPO switch and restart the UPS. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Chapter 4 Operation This chapter contains information on how to use the Powerware 9140, including front panel operation, operating modes, UPS startup and shutdown, configuring the UPS for Extended Battery Modules (EBMs), initiating the battery test, and transferring the UPS between modes.
To change the language setting, select MENU from the system status screen, then select SETUP, USER SETUP, and LANGUAGE. Scroll through the available options and press the button to select the language. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
OPERATION Display Functions When the UPS starts up, the LCD displays the Eaton Powerware logo and the type of UPS. About 5 seconds after startup or after 15 minutes of inactivity, the LCD displays the system status screen. The system status screen shows the output voltage, output frequency, output load percent, and the current operating mode (see Figure 36 on page 57).
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise, the changes do not take effect. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 69
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise, the changes do not take effect. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
OPERATION Operating Modes The Powerware 9140 front panel indicates the UPS status through the UPS indicators. Figure 36 on page 57 shows the UPS front panel indicators and controls. Figure 37 shows the internal circuit configuration. Normal Mode During Normal mode, the indicator illuminates solid and the UPS is powered from the utility.
UPS is in Standby mode. The indicator flashes slowly, indicating that power is not available to your equipment. The battery recharges when necessary. Bypass Figure 37. Internal Circuit Configuration ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary. Turn on the protected equipment. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
To start up the UPS in internal Bypass mode with utility power connected: Turn off all protected equipment before starting up the UPS. Switch on utility power where the UPS is connected. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
The UPS disconnects from the batteries and transfers to Bypass mode. To completely remove all output voltage, unplug or remove utility power from the UPS. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
SETUP, USER SETUP, and BATTERY TEST. Select to enable or disable the automatic test, choose a test period (7 to 90 days), and choose the test time (1 to 99 minutes). ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
CONTROL, OUTPUT CONTROL, and UPS TO OFF. Confirm the selection by pressing and holding the button for three seconds to select OK. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Chapter 5 Communication The Powerware 9140 UPS is equipped with a USB port, a REPO port, two DB-9 communication ports, and an X-Slot communication bay (see Figure 38). Two parallel ports are available for future use. Either the USB port or the RS-232 DB-9 communication port may be used to monitor the UPS;...
Software Suite CD. Remote Emergency Power-off and Remote On/Off The Powerware 9140 includes a two-position terminal that can be either left open or configured one of two ways: As a remote emergency power-off (REPO) contact that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location.
Page 79
REPO/ROO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size REPO/ROO 0.82–0.33 mm 0.82–0.33 mm 0 82 0.82 mm (18 AWG) (18 AWG) (18–22 AWG) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
COMMUNICATION DB-9 Communication Ports The Powerware 9140 provides two DB-9 ports on the UPS rear panel. The service port is not intended for customer use and does not support standard communication protocols. The RS-232 port is available for UPS monitoring, control, and flash upgrades.
COMMUNICATION X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 9140 has an available communication bay for one of the following X-Slot cards: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Powerware 9140 UPS battery power becomes low, Powerware LanSafe software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull them out of the EBM. Figure 41. Removing the EBM Front Cover ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 86
Figure 42. Installing the Battery Trays Replace the EBM front cover (see Figure 43) and tighten the two front cover screws. Figure 43. Replacing the EBM Front Cover ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
To remove the front cover, loosen the two front cover screws. Grasp the fingergrips on both sides of the cover and pull the cover forward firmly. Figure 44. Removing the UPS Front Cover ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 88
Replace the UPS front cover and tighten the two front cover screws. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
UPS. If you prefer to remove input power to change the electronics module, see “UPS Shutdown” on page 66. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 90
Grasp the fingergrips on both sides of the cover and pull the cover forward firmly. Turn the module lock switch to the UNLOCK position. The UPS transfers to Bypass mode. Figure 46. Removing the Electronics Module ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 91
Turn the module lock switch to the LOCK position. The UPS automatically returns to Normal mode. Replace the UPS front cover and tighten the two front cover screws. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
(4) Internal Battery Trays: 17 kg (37 lb) each Total EBM Weight: 82 kg (179 lb) Total Plug-Receptacle UPS Weight: 110 kg (240 lb) Total Hardwired UPS Weight: 107 kg (234 lb) ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 94
Hardwired Models: (4) C19, (3) C19 and (1) dual C13, each with 20A circuit breaker each with 20A circuit breaker Full Output IEC 309-60A Hardwired ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 95
Hardwired models only: TÜV/VDE, CE EMC (Class A) EN 50091-2, FCC Part 15, ICES-003 Seismic Uniform Building Code (UBC) and Bellcore for Zone 4 Earthquake ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 96
86.5 50% Load 51.5 78.5 98.5 25% Load >120 >180 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Chapter 8 Troubleshooting The Powerware 9140 is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Page 98
UPS output receptacles. the UPS on by selecting MENU from the system status screen, then select CONTROL, OUTPUT CONTROL, UPS TO ONLINE, and OK to confirm. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Page 99
Bypass mode is disabled. Check that the Allow Bypass user setting is Enabled (see page 60). ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the Help Desk for the dealer or distributor nearest you. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Powerware UPS Models: 3105, 3110, 3115, 9104, 9120, 9125, 9140, and FERRUPS up to 3.1 kVA ® WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Powerware 3105, 3110, 3115, 9104, 9120, 9125, 9140, and FERRUPS up to 3.1 kVA Products (individually...
Page 102
Product is sold, Company shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Ten-Year Pro-Rated Limited Warranty (US and Canada) Powerware UPS Models: 5115, 5125, 5140, 9104, 9120, 9125, 9140, 9155, 9170+, and FERRUPS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED WARRANTY: This pro-rated limited warranty (this “Warranty”) applies only to the original End-User (the...
Page 104
Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect. ® EATON Powerware 9140 UPS (7.5–10 kVA) User’s Guide 164201622 Rev A FINAL DRAFT 14-Jul-2006...
Powerware UPS Models 3105, 3110, 3115, 5110, 5115, 5125, 9120, 9125, 9140, 9150, 9155, 9170+, and FERRUPS GUARANTOR: The Guarantor for the load protection guaranty set forth herein is Eaton Electrical Inc., a Delaware Corporation company (“Company”). LIMITED GUARANTY: This load protection guaranty (this “Guaranty”) applies only to the original End-User (the “End-User”) of any Powerware 3105, 3110, 3115, 5110, 5115, 5125, 9120, 9125, 9140, 9150, 9155, 9170+, and...