INSTALLATION
This connector must only be connected to an IEC 60950 safety extra low voltage (SELV)
circuit. This circuit must be separated from any hazardous voltage circuits by reinforced
insulation.
4.
NOTE For REPO, a separate contact must simultaneously cause UPS input AC power to be
removed.
5.
6.
7.
8.
9.
10. Activate the external REPO or ROO switch to test the function.
11. REPO only. De-activate the external REPO switch and restart the
56
EATON Powerware
Connect the switch or circuit to the REPO connector using
2
non-shielded 0.82 mm
Verify that the externally-connected REPO or ROO switch is not
activated to enable power to the UPS output receptacles.
Plug in or apply utility power to the UPS. The UPS enters Standby
mode.
To configure the UPS for REPO behavior, select MENU from the
system status screen, then select SETUP, USER SETUP, and
CONTACT CONFIG.
Set CONTACT USAGE to REPO. Then set CONTACT TYPE to either
normally-open (N/O) or normally closed (N/C).
To configure the UPS for ROO behavior, select MENU from the system
status screen, then select SETUP, USER SETUP, and
CONTACT CONFIG.
Set CONTACT USAGE to REMOTE ON/OFF. Then set CONTACT
TYPE to either normally-open (N/O) or normally closed (N/C).
REPO only. Start the UPS by selecting MENU from the system
status screen, then select CONTROL, OUTPUT CONTROL,
UPS TO ONLINE, and OK to confirm.
Verify the status change on the UPS display.
UPS.
®
9140 UPS (7.5–10 kVA) User's Guide
W A R N I N G
2
–0.33 mm
(18–22 AWG) wire.
S
164201622 Rev A FINAL DRAFT 14-Jul-2006