INSTALLATION
6.
7.
8.
9.
Table 1. UPS Input Wiring Specifications
UPS Terminal
Terminal
Block
Position
Input
1
2
3
4
5
1
2
Use 13.3 mm
(6 AWG) 90_C copper wire minimum. For ease of installation, use appropriately sized ferrules on the end
of each wire.
2
For single-phase 208V only, in North America and Japan, utility L2 connects to UPS neutral; for most other countries
(200, 220-240V), utility neutral connects to UPS neutral.
3
The ground screw on the input terminal block can be used for input ground if an appropriate ring lug is available.
50
EATON Powerware
Punch holes in the terminal block covers for the input, input bypass
(dual input feed only), and output conduit using a Greenlee
or similar device. The holes accommodate up to 2I IMC conduit.
Pull the input, input bypass (dual input feed only), and output wires
through separate conduit, leaving approximately 15 cm (6") of
exposed wire. Attach a flexible metal fitting to the end of each
conduit.
Insert each conduit through a wiring access entry and attach the
conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the
end of each incoming wire.
Connect the input and ground wires to the input terminal block
according to Figure 32 and Table 1.
L1 In
Figure 32. UPS Input Terminal Block
UPS Wire Function
L1 In
L2 In
L3 In
2
Neutral In
3
Input Ground
®
9140 UPS (7.5–10 kVA) User's Guide
L2 In
L3 In
Neutral In
Input Ground
Terminal Wire
1
Size Rating
2
2
13.3 mm
13 3
(6 AWG)
(6 AWG)
S
164201622 Rev A FINAL DRAFT 14-Jul-2006
punch
®
Tightening
Torque
1.8 Nm (16 lb in)
1 8 N (16 lb i )