Eaton Powerware 9125 Two-in-One UPS 5000 User Manual
Eaton Powerware 9125 Two-in-One UPS 5000 User Manual

Eaton Powerware 9125 Two-in-One UPS 5000 User Manual

Two-in-one ups 5000/6000 va
Hide thumbs Also See for Powerware 9125 Two-in-One UPS 5000:

Advertisement

Powerware 9125 Two-in-One UPS
®
5000/6000 VA
User's Guide

Advertisement

Table of Contents
loading

Summary of Contents for Eaton Powerware 9125 Two-in-One UPS 5000

  • Page 1 Powerware 9125 Two-in-One UPS ® 5000/6000 VA User’s Guide...
  • Page 2 Powerware, ABM, and FERRUPS are registered trademarks and X-Slot, ConnectUPS, and LanSafe are trademarks of Eaton Power Quality Corporation. Greenlee is a registered trademark of Greenlee Textron. Modbus is a registered trademark of Modicon.
  • Page 3 Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits 93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC...
  • Page 4 Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such as important operating and maintenance instructions.
  • Page 5: Table Of Contents

    ............. . . EATON Powerware .
  • Page 6 Ten-Year Pro-Rated Limited Warranty (US and Canada) Load Protection Guarantee (US and Canada) ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com ..........
  • Page 7: Introduction

    — causing hours of lost productivity and expensive repairs. With the Powerware 9125, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Figure 1 shows the Powerware 9125 UPS with an optional Extended Battery Module (EBM).
  • Page 8 INTRODUCTION Providing outstanding performance and reliability, the Powerware 9125’s unique benefits include the following: Online UPS design with pure sine wave output. The UPS filters and regulates incoming AC power and provides consistent power to your equipment without draining the battery.
  • Page 9: Safety Warnings

    For UPS models with hardwired outputs, suitably rated disconnect switches for the output AC circuit(s) are to be provided by others. EATON Powerware IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS D A N G E R W A R N I N G ®...
  • Page 10 For UPS systemer med hårdledningsudgange, skal egnede, nominelle afbryderkontakter for vekslestrømmens udgangskredsløb forsynes af andre. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com C A U T I O N F A R E...
  • Page 11: Belangrijke Veiligheidsinstructies

    Voor UPS systemen met vast-bedrade uitgangen, moeten de juiste hoofdschakelaars voor wisselstroom uitvoercircuit(s) door anderen worden geleverd. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide SAFETY WARNINGS A D V A R S E L...
  • Page 12: Tarkeita Turvaohjeita

    Noudata asianmukaisia ohjeita. Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä. Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com O P G E L E T V A A R A...
  • Page 13 Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide SAFETY WARNINGS D A N G E R ! A V E R T I S S E M E N T !
  • Page 14 Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen Bestimmungen zu beachten. Batterien niemals verbrennen, da sie explodieren können. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com W A R N U N G A C H T U N G...
  • Page 15: Avvisi Di Sicurezza

    Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide SAFETY WARNINGS P E R I C O L O A V V E R T E N Z A...
  • Page 16: Viktig Sikkerhetsinformasion

    Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av batterier. Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com F A R L I G...
  • Page 17 Nunca jogue as baterias no fogo, porque há risco de explosão. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide SAFETY WARNINGS C U I D A D O A D V E R T Ê...
  • Page 18 СОХРАНИТЕ ЭТИ УКАЗАНИЯ ДАННОЕ РУКОВОДСТВО СОДЕРЖИТ ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com О П А С Н О П Р Е Д У П Р Е Ж Д Е Н И Е...
  • Page 19: Advertencias De Seguridad

    Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide SAFETY WARNINGS P E L I G R O A D V E R T E N C I A P R E C A U C I Ó...
  • Page 20 Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com F A R A V A R N I N G...
  • Page 21: Installation

    UPS Setup The Powerware 9125 UPS is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. For rack-mounted installations, follow the instructions with the rail kit before installing the internal batteries.
  • Page 22: Installing The Ups Internal Batteries

    (see Figure 3). Install the UPS front covers (provided in the accessory kit). See Figure 4. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com C A U T I O N Figure 2.
  • Page 23: Tower Setup

    Figure 5. Installing the UPS Pedestals Carefully position the cabinet upright (see Figure 6). Continue to “Plug-Receptacle UPS Installation” on page 21 or “Hardwired UPS Installation” on page 24. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide INSTALLATION 164201513 Rev B www.powerware.com...
  • Page 24 NOTE The EBM(s) must be installed to the right of the UPS as shown in Figure 7. Joining brackets are required for installations with two or more cabinets. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com Figure 6. UPS Cabinet with Pedestals Figure 7.
  • Page 25: Ebm Installation

    EBM. Repeat for each additional EBM. Up to four EBMs may be connected to the UPS. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide Figure 8. Installing the Joining Brackets (Top View) C A U T I O N 164201513 Rev B www.powerware.com...
  • Page 26 Continue to the following section, “Plug-Receptacle UPS Installation,” or “Hardwired UPS Installation” on page 24. Battery Circuit Breaker Battery Circuit Breakers ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com Figure 9. Typical EBM Installation 164201513 Rev B UPS Battery...
  • Page 27: Plug-Receptacle Ups Installation

    If an emergency power-off (disconnect) switch is required by local codes, see “Remote Emergency Power-off Installation” on page 22 to install the REPO switch before powering on the UPS. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide USB Port Communication Port...
  • Page 28: Remote Emergency Power-Off Installation

    Virtual Front Panel UPS utility on the Software Suite CD. Remote Emergency Power-off Installation The Powerware 9125 includes a REPO connector that allows power to be switched off at the UPS output from a customer-supplied switch in a remote location.
  • Page 29 On button. Activate the external REPO switch to test the REPO function. De-activate the external REPO switch and restart the UPS. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide INSTALLATION C A U T I O N –0.5 mm...
  • Page 30: Hardwired Ups Installation

    NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your equipment and void your warranty. The Powerware 9125 hardwired models require a dedicated branch circuit that meets the following requirements: 40A minimum circuit with short circuit and overcurrent protection 200–240 Vac...
  • Page 31 Insert each conduit through a wiring access entry and attach the conduit fitting to the panel. Strip 1.5 cm (0.5I) of insulation from the end of each incoming wire. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide INSTALLATION punch or similar device.
  • Page 32 Block Position Input No Connection Output * Use 2.0 mm (14 AWG) 75_C copper wire minimum. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com No Connection L2/Neutral In L1 Out L1 In Input Figure 13. UPS Terminal Block...
  • Page 33 NOTE If you installed power management software and optional EBMs, ensure maximum battery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide INSTALLATION ) position.
  • Page 34 INSTALLATION ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com 164201513 Rev B...
  • Page 35: Operation

    To turn on the UPS without using utility power, press and hold the On button for approximately three seconds. The UPS supplies power to your equipment and goes into Battery mode. EATON Powerware μ indicator illuminates solid and the bar ®...
  • Page 36: Turning The Ups Off

    The UPS cycles the bar graph indicators twice, verifies the battery converter, and schedules the battery test to occur within 24 hours. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com button while the UPS is in Battery mode causes the UPS to shut button for approximately three seconds.
  • Page 37: Transferring The Ups To Bypass Mode

    Press the On button again for approximately three seconds to return to Normal mode. Operating Modes Powerware 9125’s front panel indicates the UPS status through the UPS indicators. Figure 14 shows the UPS front panel indicators and controls. Normal Mode Indicator...
  • Page 38: Normal Mode

    When all of the bar graph indicators are illuminated and the flashes, power requirements exceed UPS capacity; see page 53 for more information. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com μ indicator illuminates and the front panel <10%...
  • Page 39: Battery Mode

    When utility power is restored after the UPS shuts down, the UPS automatically restarts. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide OPERATION indicator illuminates. The front panel >75%...
  • Page 40: Bypass Mode

    The battery recharges when necessary. NOTE For 208–240V models, the output receptacles may remain electrically live (up to 110–120V). Unplug the UPS to ensure power is not available to the output receptacles. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com μ...
  • Page 41: Configuration

    NOTE The UPS exits Configuration mode automatically after two minutes of inactivity. Press and hold the On button and the for three seconds to exit Configuration mode at any time. EATON Powerware button) to modify the UPS configuration. Figure 17 C A U T I O N button while the UPS is in Configuration mode;...
  • Page 42 220V Nominal Output Voltage 208V Nominal Output Voltage Site Wiring Fault Alarm ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com Bar Graph Indicators & Press and hold the On and Test/Alarm Reset buttons simultaneously for three seconds to toggle between Configuration and Operation modes.
  • Page 43: Communication

    Chapter 6 Communication The Powerware 9125 UPS is equipped with a USB port, a DB-9 communication port, and an X-Slot communication bay (see Figure 18). Either the USB port or the DB-9 communication port may be used to monitor the UPS; however, they cannot operate simultaneously.
  • Page 44: Db-9 Communication Port

    AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Power Source +V (8 to 24 volts DC power) ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com Figure 19. Communication Port Direction from the UPS —...
  • Page 45: X-Slot Cards

    X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Powerware 9125 has an available communication bay for one of the following X-Slot cards: ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface;...
  • Page 46 COMMUNICATION ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com 164201513 Rev B...
  • Page 47: Ups Maintenance

    UPS. Contact your service representative. When to Replace Batteries When the Contact your service representative to order new batteries. EATON Powerware indicator flashes, the batteries may need replacing. ® 9125 Two-in-One UPS (5000/6000 VA) User’s Guide 164201513 Rev B...
  • Page 48: Replacing Batteries

    If the UPS is in a tower configuration, remove the joining brackets. If the UPS is in a rack, attach the supplied mounting brackets to the new EBM. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com button for approximately three seconds, then unplug or...
  • Page 49 Switch all battery circuit breakers to the ON ( Joining Brackets Battery Circuit Breakers EBM Battery Connectors Figure 21. EBM Connections ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide UPS MAINTENANCE ) position. Battery Circuit Breaker Cables UPS Battery Connector 164201513 Rev B...
  • Page 50: How To Replace Internal Batteries

    Pull the battery trays out onto a flat, stable surface (see Figure 24). See “Recycling the Used Battery or UPS” on page 46 for proper disposal. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com C A U T I O N Figure 22.
  • Page 51: Testing New Batteries

    The UPS cycles the bar graph indicators twice, verifies the battery converter, and schedules the battery test to occur within 24 hours. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide UPS MAINTENANCE button for three 164201513 Rev B www.powerware.com...
  • Page 52: Recycling The Used Battery Or Ups

    Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com W A R N I N G...
  • Page 53: Specifications

    Table 5. Electrical Input Nominal Voltage Voltage Range Nominal Frequency Noise Filtering Connections Input Power Factor EATON Powerware Power Levels (Rated at Nominal Inputs) 5000 VA 3500W 5000 VA, 3500W 6000 VA, 4200W 6000 VA 4200W 208, 220, 230, 240V auto-sensing 160–288V nominal...
  • Page 54 Communication Surge Suppression Safety Conformance Agency Markings EMC (Class A) ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com Nominal output voltage ±3% Nominal output voltage ±3% Normal mode: Sine wave; <3% THD with linear or PFC load;...
  • Page 55 2000 VA/1400W 37.7 NOTE Battery times are approximate and vary depending on the load configuration and battery charge. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide Extended Battery Module (EBM) 44.2 x 68.3 x 21.8 cm 17.4” x 26.9” x 8.6” (5U) (20) 12V, 7.2 Ah internal batteries...
  • Page 56 SPECIFICATIONS ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com 164201513 Rev B...
  • Page 57: Troubleshooting

    Before silencing an alarm, check the alarm condition and perform the applicable action to resolve the condition (see Table 11). To silence the alarm for an existing fault, press the status changes, the alarm beeps, overriding the previous alarm silencing. EATON Powerware Site Wiring Fault Overtemperature Overload Figure 25.
  • Page 58 Three-minute battery warning. Warning - Low Battery Shutdown imminent. Shutdown - Low Battery ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com Action Check the power cord connections. Have a qualified electrician test and repair the outlet. Press the On button to supply power to the connected equipment.
  • Page 59 30 seconds) or the load is Overload defective. Continuous audible alarm ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide TROUBLESHOOTING Action The equipment is transferred to utility power; however, the utility power continues to be passively filtered by the UPS.
  • Page 60: Service And Support

    A replacement or repair unit will be shipped, freight prepaid for all warrantied units. NOTE For critical applications, immediate replacement may be available. Call the Desk for the dealer or distributor nearest you. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com 1-800-356-5737 1-919-870-3149 1-800-461-9166 ext 260...
  • Page 61: Warranty

    This limited warranty (this “Warranty”) applies only to the original End-User (the “End-User”) of any Powerware 3105, 3110, 3115, 9104, 9120, 9125, and FERRUPS up to 3.1 kVA Products (individually and collectively, the “Product”) purchased on or after June 1, 2004 and cannot be transferred. This Warranty applies even in the event that the Product is initially sold by Company for resale to an End-User.
  • Page 62 Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com This Warranty does not cover any defects or damages...
  • Page 63: Ten-Year Pro-Rated Limited Warranty (Us And Canada)

    In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, call your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3149. For comments or questions about this Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.
  • Page 64 Product’s operation and maintenance manual; and protect against further damage to the Product if there is a covered defect. ® EATON Powerware 9125 Two-in-One UPS (5000/6000 VA) User’s Guide www.powerware.com This Warranty does not cover any defects or damages...
  • Page 65: Load Protection Guarantee (Us And Canada)

    In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3149. Company will not accept any Product for return, credit or exchange unless expressly authorized by Company in writing and delivered FOB Company factory.
  • Page 66 In the USA, call the Customer Reliability Center 7x24 at 800-356-5737. Outside of the USA, contact your local Powerware product sales or service representative, or call the Customer Reliability Center in the USA at 919-870-3149. For comments or questions about this Load Protection Guaranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.