Powerware 9125 (9910-E30) UPS ® ® Installation Guide for IBM Applications...
Page 2
Corporation or its subsidiaries and affiliates. Burndy is a registered trademark of Framatone Connectors International. ECopyright 2007 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton Corporation.
..........® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications...
Page 4
TABLE OF CONTENTS This page intentionally left blank. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
E30 Accessory Kit * If the UPS is factory-installed in an IBM rack, these items are pre-assembled. Table 2. E30 Application Matrix iSeries iSeries pSeries ® pSeries pSeries iSeries Eaton PN Description Tower Tower Tower Tower Rack Rack NEMA NEMA —...
Page 6
Table 4. E30 Accessory Kit (42R8070) Quantity Eaton PN Description 164201374 Powerware 9125 Two-in-One UPS (2500/3000 VA) User’s Guide 164201696 Powerware 9125 (9910-E30) Installation Guide for IBM Applications 152601942-001 IEC 320-C13 to C14, 10A Equipment Power Cords (2m/6.6 ft) 152601971-001 IEC 320-C19 to C20, 16A Equipment Power Cord (4.5m/14.8 ft)
Page 7
* If the EBM is factory-installed in an IBM rack, these items are pre-assembled. Table 6. E30 6644 EBM Accessory Kit (42R8072) Quantity Eaton PN Description 164201375 Powerware 9125 Two-in-One EBM (2500/3000 VA) User’s Guide 130500110-001 Mounting Handles × 180500200-002 Mounting Handle Screws (#8-32 1/2”)
NOTE The UPS and any optional cabinets MUST be installed at the bottom of the rack. If placed in a rack with existing equipment, the rack must be reconfigured to allow the UPS installation at the bottom of the rack. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 10
Insert the screws through positions 3 and 4 of the rail (see Figure 5). NOTE Do not tighten the screws until the UPS or EBM is installed. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 11
The bottom rail uses positions 2 and 4 for the rear hex-head screws. If you are installing additional rails, place the next rail 4 holes above the last installed screw. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 12
Tighten the assembly wing nuts on both rail assemblies. Place the UPS on a flat, stable surface with the front of the UPS facing toward you. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 13
NOTE The PDM must be installed above the UPS. The EBMs must be installed below the UPS as shown in Figure 9. Figure 9. Rack-Mount UPS with PDM and EBM ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 14
(see Step 3 on page 6). 15. Continue to “EBM Installation” on page 15, “PDM Installation” on page 17, or “Power Connections and Startup” on page 20. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Figure 12. Installing UPS Pedestals (for One Cabinet) Carefully position the cabinet upright with the air vents at the top (see Figure 13). Continue to “UPS Installation” on page 18. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 16
Figure 14. Installing UPS Pedestals Place the EBM upside down so that the right end of the cabinet is accessible (see Figure 15). Figure 15. Installing EBM Pedestals ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 17
Carefully position the cabinets upright with the air vents at the top (see Figure 18 or Figure 19). Air Vents UPS with EBM UPS with PDM Figure 18. Pedestals with Two Cabinets ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 18
10. If installing additional cabinets, repeat Step 9 for each cabinet. 11. Continue to the following section, “EBM Installation” or “PDM Installation” on page 17. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
NOTE Keep the EBM cable cover and screws for future use. If the EBM is stored or removed from the UPS, the EBM cable cover must be installed as a safety precaution. EBM Cable with Cover Figure 22. EBM Cable Cover ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 20
Repeat for each additional EBM. Up to four EBMs may be connected to the UPS. Continue to the following section, “PDM Installation” or “UPS Installation” on page 18. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Any devices that are operating on battery power are also shut down immediately. When the REPO switch is reset, the equipment will not return to battery power until the UPS is manually restarted. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 23
Use stranded, non-shielded wiring, size 0.75 mm –0.5 mm (18–20 AWG). NOTE A separate contact must simultaneously cause UPS input AC power to be removed. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Legend (Figure 27, Figure 28, and Figure 29) UPS to utility (mains) power cord Device to UPS power cord Device to utility (mains) power cord ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 25
UPS. Distribute the load evenly between the rows of receptacles on the UPS. NOTE The redundant power source must be protected with Transient Voltage Surge Suppression (TVSS). ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 26
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 27
Submit your question to our FAQ database at www.powerware.com/Iibm and select General Knowledge > Frequently Asked Questions Contact the IBM office or Business Partner servicing your account ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Output power (UPS to device) cords, located in the E30 accessory kit Qty. IEC 320-C13 to C14, 1.8m (6 ft) IEC 320-C19 to C20, 2.7m (9 ft) Mains iSeries or Varies Eaton (6) pSeries Device 2100W iSeries or Eaton (6) pSeries Device(s) Figure 30.
Page 29
Dual-redundant power options: 1. Device or PDU to mains (no UPS protection), then MUST have Transient Voltage Surge Suppression (TVSS) on mains. Mains 2. Second E30. Varies Eaton (6) iSeries or pSeries Device 2100W Second Mains E30 or Eaton (6)
Page 30
Output power (UPS to device) cords, located in the E30 accessory kit Qty. IEC 320-C13 to C14, 1.8m (6 ft) IEC 320-C19 to C20, 2.7m (9 ft) Varies: Device country-specific power (mains) cord ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 31
INSTALLATION Dual-redundant power options: 1. Device or PDU to mains (no UPS protection), then MUST have Transient Voltage Surge Suppression (TVSS) on mains. 2. Second E30. Mains Varies Eaton (6) iSeries or pSeries Device 2100W Mains Eaton (6) iSeries or...
Page 32
Device(s) E30 UPS 2100W with iSeries or FC 6570 pSeries Device(s) iSeries or pSeries Device(s) Figure 33. E30 and FC 6570 PDM NEMA Countries Tower ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
PDM bypass switch is returned to the NORMAL position. Load Segment 1 Load Segment 2 Figure 34. UPS Load Segments ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 34
INSTALLATION This page intentionally left blank. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
On button for at least four seconds. The UPS supplies power to your equipment and goes into Battery mode. When the UPS starts on battery, it does not conduct a self-test to conserve battery power. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
During the five-second test, the bar graph indicators cycle through twice. If the alarm beeps or a UPS alarm indicator stays on, refer to “Troubleshooting” in the Powerware 9125 Two-in-One UPS (2500/3000 VA) User’s Guide. ®...
OPERATION Operating Modes The Powerware 9125’s front panel indicates the UPS status through the UPS indicators. Figure 35 shows the UPS front panel indicators and controls. Normal Mode Indicator Alarm Indicators Bar Graph Indicators Battery Mode Indicator Bypass Mode Indicator...
Figure 36. Load Level Indicators When all of the bar graph indicators are illuminated and the indicator flashes, power requirements exceed UPS capacity; refer to “Troubleshooting” in the Powerware 9125 Two-in-One UPS (2500/3000 VA) User’s Guide for more information. ® ®...
When utility power is restored after the UPS shuts down, the UPS automatically restarts. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
NOTE For 220–240V models, the output receptacles may remain electrically live (up to 110–120V). Unplug the UPS to ensure power is not available to the output receptacles. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
NOTE The UPS exits Configuration mode automatically after two minutes of inactivity. Press the On button and the button simultaneously to exit Configuration mode at any time. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 42
Configuration and Operation modes. Test/Alarm On Button Reset Button Press the On button to scroll to the next option. Figure 38. Using Configuration Mode ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 43
On (default) Alarm sounds when there is an AC input failure. Alarm Alarm Flashing Alarm DOES NOT sound when there is an AC input failure. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 44
OPERATION This page intentionally left blank. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
The cable pins are identified in Figure 39 and the pin functions are described in Table 14. Figure 39. Communication Port ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 46
Figure 40. Removing the Single-Port Card Move the J3 jumper to the AS/400 position to enable the ® On-Bypass relay as shown in Figure 41. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 47
Align the Single-Port Card with the slot guides and slide the card into the slot until it is firmly seated. Secure the Single-Port Card with the screws removed in Step 1. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Select the Battery tab, then select the number of EBMs you are using from the pull-down menu (you can choose up to four EBMs). Click OK and close the software. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
To connect the UPS to an i5, iSeries, or AS/400 and a serial server you need: An Eaton-supplied Relay-Serial Card, an AS/400 interface cable (labeled 152601976-001), and a serial interface cable (labeled 124102044-001), located in the FC 2939 carton labeled “Cable Kit for IBM iSeries and Windows or AIX/Linux Servers”...
Page 50
Serial (TTY) Server Serial Interface Cable (labeled 124102044-001) AS/400 Interface Cable (labeled 152601976-001) Relay-Serial Card Communication Port Figure 43. iSeries or AS/400 and Serial Server Interface ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Serial (TTY) Interface Overview ® To serially (TTY) connect the UPS to a p5, pSeries, RS/6000 OpenPower or other system you need: An Eaton-supplied serial interface cable (labeled 124102044-001), located in the E30 accessory kit Powerware LanSafe Power Management Software from the ®...
Logical Partitions Interface Overview To connect the UPS to a p5 or pSeries with LPARs you need: An Eaton-supplied ConnectUPS-X Web/SNMP Card, located in the FC 2934 carton labeled “ConnectUPS-X Web/SNMP Card Kit” NetWatch software from the Software Suite CD, located in the E30...
Figure 46. Example of IBM Serial Number Labels Comments We welcome your comments about this manual. Please send your questions or suggestions for improvements to ibm.ups@powerware.com. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
SERVICE AND SUPPORT This page intentionally left blank. ® ® EATON Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications 164201696 Rev 1...
Page 55
92/31/EEC, Amending Directive 89/336/EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact: Eaton Power Quality Oy Koskelontie 13 FIN-02920 Espoo Finland...