Eaton Powerware 9140 User Manual page 94

7.5-10 kva ups
Hide thumbs Also See for Powerware 9140:
Table of Contents

Advertisement

SPECIFICATIONS
Table 9. Electrical Input
Nominal Voltage
Voltage Range
Nominal Frequency
Frequency Range
Default Frequency
Maximum Input Current at
Nominal Utility Voltage
Noise Filtering
Connections
Input Power Factor
Input Mode
Table 10. Electrical Output
Regulation
Nominal Outputs
Output Overload
Voltage Waveform
Output Receptacles
Full Output
86
EATON Powerware
200/208/220/230/240V auto-sensing
60 Hz (50 Hz for hardwired model, 220–240V)
(not applicable for hardwired models)
MOVs and line filter for normal and common mode noise
3-meter IEC 309-60A power cord or hardwired
Single-phase or three-phase (three-phase option on hardwired models only)
Nominal output voltage ±2% Static, ±10% Dynamic
(voltage configurable or auto-sensing)
110–130%: load transfers to Bypass mode after 1 minute
130–150%: load transfers to Bypass mode after 1 second
>150%: load transfers to Bypass mode after 1 ms
Normal mode: Sine wave; <3% THD with linear load;
Plug-Receptacle Models:
(4) C19,
each with 20A circuit breaker
IEC 309-60A
®
9140 UPS (7.5–10 kVA) User's Guide
160–253V, 174–288V
50/60 Hz auto-sensing
45–65 Hz
48A
>0.99
200/208/220/230/240V
45/48/45/43/41A
9/10/10/10/10 kVA
7.2/8/8/8/8 kW
<5% with nonlinear load
Hardwired Models:
(3) C19 and (1) dual C13,
each with 20A circuit breaker
Hardwired
S
164201622 Rev A FINAL DRAFT 14-Jul-2006