Table 5. User Settings (continued)
Description
Bypass Freq Dev
(Bypass Frequency Deviation Limits)
Qualify Bypass
Allow Bypass
Set Baud Rate
Set Site (Wiring) Fault
Contact Config*
* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,
the changes do not take effect.
®
EATON Powerware
9140 UPS (7.5–10 kVA) User's Guide
Available Settings
1 through 5 Hz (1 Hz increments)
NOTE This value sets the limits from 1 Hz to
5 Hz of the nominal output configuration. The
value cannot be set lower than the current
Utility Sync Window limit defined in the
Service Menu.
[Enabled][Disabled]
NOTE This setting enables or disables the
bypass qualification rules. If the UPS is not
able to sync with the Bypass utility, the value
is Enabled even if set to Disabled. No transfer
to an out-of-sync Bypass utility is permitted.
[Enabled][Disabled]
Port 1 (RS232): [19200] [9600] [2400] [1200]
Port 2 (SERVICE): [19200] [9600] [2400] [1200]
[Enabled][Disabled]
Contact Usage: [REPO][ROO][Disabled]
Contact Type: [N/O][N/C]
S
164201622 Rev A FINAL DRAFT 14-Jul-2006
OPERATION
Default Setting
5 Hz
Enabled
Enabled
9600
Disabled
REPO
N/O
61