Eaton Powerware 9140 User Manual page 98

7.5-10 kva ups
Hide thumbs Also See for Powerware 9140:
Table of Contents

Advertisement

TROUBLESHOOTING
Alarm or Condition
On Bypass
LED is on.
1 long beep every 5 seconds.
Bypass Unavailable
LED is flashing slowly.
1 long beep every 5 seconds.
Battery Connection
LED is on.
1 long beep every 5 seconds.
Overload
LED is on.
1 long beep every 5 seconds.
Overtemperature
LED is on.
1 long beep every 5 seconds.
Site Wiring Fault
LED is on.
1 long beep every 5 seconds.
The UPS does not provide the
expected backup time.
Power is not available at the
UPS output receptacles.
90
EATON Powerware
Possible Cause
The UPS is in Bypass mode.
Bypass is not available because
the bypass input utility is outside
the configured bypass range.
The UPS does not recognize the
internal batteries.
A battery tray is disconnected.
Power requirements exceed the
UPS capacity (greater than
100% of nominal; see page 86 for
specific output overload
ranges).
The UPS internal temperature is
too high or a fan has failed.
Ground wire connection does
not exist, or the line and neutral
wires are reversed in the wall
outlet.
The batteries need charging or
service.
The UPS is in Standby mode.
®
9140 UPS (7.5–10 kVA) User's Guide
Action
The equipment transferred to bypass utility power.
Battery mode is not available; however, the utility
power continues to be passively filtered by the
UPS. Check for one of the following alarms:
overtemperature, overload, UPS failure, hot swap,
or remote emergency power-off (REPO).
Check the bypass utility. The UPS is receiving
bypass utility power that may be unstable or in
brownout conditions. The UPS continues to supply
power to your equipment. Check for one of the
following alarms: bypass over or under voltage,
bypass over or under frequency, or bypass
unvailable.
If the condition persists, contact your service
representative.
Verify that all battery trays are fully seated and
locked in place. If the condition persists, contact
your service representative.
Remove some of the equipment from the UPS. The
UPS continues to operate, but may switch to
Bypass mode if the load increases. The alarm
resets when the condition becomes inactive.
Shut down the UPS. Clear vents and remove any
heat sources. Allow the UPS to cool. Ensure the
airflow around the UPS is not restricted. Restart the
UPS. If the condition persists, contact your service
representative.
Have a qualified electrician correct the wiring.
Apply utility power for 48 hours to charge the
batteries. If the condition persists, contact your
service representative.
Supply power to the connected equipment: Turn
the UPS on by selecting MENU from the system
status screen, then select CONTROL, OUTPUT
CONTROL, UPS TO ONLINE, and OK to confirm.
S
164201622 Rev A FINAL DRAFT 14-Jul-2006

Advertisement

Table of Contents
loading

Table of Contents