INSTALLATION
21. Turn the UPS on by selecting MENU from the system status
22. If you installed an optional REPO or ROO, test the REPO or ROO
23. If optional EBMs are installed, continue to "Configuring the UPS for
NOTE The batteries charge to 80% capacity in less than 5 hours. However, it is
recommended that the batteries charge for 48 hours after installation or long-term storage.

REPO and ROO Installation

The Powerware 9140 includes a two-position terminal (see Figure 35)
that can be either left open or configured one of two ways:
S
S
54
EATON Powerware
screen, then select CONTROL, OUTPUT CONTROL, UPS TO
ONLINE, and OK to confirm.
The
indicator illuminates solid. The UPS is now in Normal mode
and supplying power to your equipment.
If the alarm beeps or a UPS alarm indicator stays on, see
"Troubleshooting" on page 89.
function:
Activate the external REPO or ROO switch. Verify the status
change on the UPS display.
Deactivate the external REPO or ROO switch and restart the UPS.
EBMs" on page 67.
As a remote emergency power-off (REPO) contact that allows power to be
switched off at the UPS output from a customer-supplied switch in a
remote location.
As a remote on/off (ROO) contact that allows the UPS to be turned on
and off from a customer-supplied switch in a remote location.
Figure 35. REPO/ROO Connection
®
9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev A FINAL DRAFT 14-Jul-2006