INSTALLATION
Hardwired UPS Installation
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
S
S
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to
your equipment and void your warranty.
The Powerware 9125 hardwired models require a dedicated branch
circuit that meets the following requirements:
S
S
S
S
S
S
24
EATON Powerware
www.powerware.com
For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
40A minimum circuit with short circuit and overcurrent protection
200–240 Vac
Single-phase
50/60 Hz
The breaker must be wall-mounted and be readily accessible to the
operator
Flexible metal conduit (recommended for ease of service and
maintenance)
®
9125 Two-in-One UPS (5000/6000 VA) User's Guide
W A R N I N G
C A U T I O N
S
164201513 Rev B