INSTALLATION
Installing the EBM Batteries
To install the battery trays into the EBM cabinet:
1.
2.
3.
28
EATON Powerware
Verify that the battery circuit breakers on the EBM rear panel are in
the OFF (O) position (see Figure 26 on page 41).
Remove the EBM front cover (see Figure 11).
To remove the front cover, loosen the two front cover screws.
Grasp the fingergrips on both sides of the cover and pull the cover
forward firmly.
Figure 11. Removing the EBM Front Cover
Slide the battery trays into the cabinet (see Figure 12). Push each
tray in until the battery tray lock on the handle catches to lock the
tray in place.
Figure 12. Installing the Battery Trays
®
9140 UPS (7.5–10 kVA) User's Guide
S
164201622 Rev A FINAL DRAFT 14-Jul-2006
Battery Tray
Lock