INSTALLATION

Hardwired UPS Installation

34
Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide
www.eaton.com/powerquality
Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
S
For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.
S
For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.
NOTE Do not make unauthorized changes to the UPS or accessories; otherwise, damage
may occur to your equipment and void your warranty.
The Eaton 5125 hardwired models require a dedicated branch circuit that
meets the following requirements:
S
40A minimum circuit with short circuit and overcurrent protection
S
200–240 Vac
S
Single-phase
S
50/60 Hz
S
The breaker must be wall-mounted and readily accessible to the
operator
S
Flexible metal conduit (recommended for ease of service and
maintenance)
W A R N I N G
C A U T I O N
S
164201541 Rev D