Table 11. Environmental and Safety
Operating Temperature
Storage Temperature
Transit Temperature
Relative Humidity
Operating Altitude
Transit Altitude
Heat Dissipation
Audible Noise
Leakage Current
Communication
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
Seismic
®
EATON Powerware
9140 UPS (7.5–10 kVA) User's Guide
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
-20°C to 50°C (-4°F to 122°F)
-20°C to 50°C (-4°F to 122°F)
0–95% noncondensing
Up to 3,000 meters above sea level
Up to 15,000 meters above sea level
2066 BTU/hr maximum
Less than 55 dBA at 5 feet with battery fully charged, without horn
< 3.5 mA
DB-9: 1200-19200 baud; USB 1.1 compliant
ANSI C62.41 Category B3
UL 1778; CSA C22.2, No. 107.3;
EN and IEC 62040-2; NOM-019-SCFI-1993;
EN and IEC 62040-1-1 (Hardwired models only);
EN and IEC 60950-1 (Hardwired models only)
cULus, cUL, NOM
Hardwired models only: TÜV/VDE, CE
EN 50091-2, FCC Part 15, ICES-003
Uniform Building Code (UBC) and Bellcore for Zone 4 Earthquake
S
164201622 Rev A FINAL DRAFT 14-Jul-2006
SPECIFICATIONS