Eaton Powerware 9140 User Manual page 53

7.5-10 kva ups
Hide thumbs Also See for Powerware 9140:
Table of Contents

Advertisement

9.
To change the factory-set defaults, see "User Settings" on
page 60.
10. Turn the UPS on by selecting MENU from the system status
screen, then select CONTROL, OUTPUT CONTROL, UPS TO
ONLINE, and OK to confirm.
The
and supplying power to your equipment.
If the alarm beeps or a UPS alarm indicator stays on, see
"Troubleshooting" on page 89.
11. If you installed an optional REPO or ROO, test the REPO or ROO
function:
Activate the external REPO or ROO switch. Verify the status
change on the UPS display.
Deactivate the external REPO or ROO switch and restart the UPS.
12. If optional EBMs are installed, continue to "Configuring the UPS for
EBMs" on page 67.
NOTE The batteries charge to 80% capacity in less than 5 hours. However, it is
recommended that the batteries charge for 48 hours after installation or long-term storage.
®
EATON Powerware
9140 UPS (7.5–10 kVA) User's Guide
indicator illuminates solid. The UPS is now in Normal mode
S
164201622 Rev A FINAL DRAFT 14-Jul-2006
INSTALLATION
45