10. Connect the input bypass and ground wires to the input bypass
Table 2. UPS Input Bypass Wiring Specifications
UPS Terminal
Terminal
Block
Position
Input Bypass
1
2
3
4
2
* Use 13.3 mm
(6 AWG) 90_C copper wire minimum. For ease of installation, use appropriately sized ferrules on the end
of each wire.
®
EATON Powerware
9140 UPS (7.5–10 kVA) User's Guide
terminal block according to Figure 33 and Table 2.
L1-JP
Figure 33. UPS Input Bypass Terminal Block
UPS Wire Function
L1-JP
Line In
Neutral In
Input Bypass Ground
S
164201622 Rev A FINAL DRAFT 14-Jul-2006
Line In Neutral In
Input Bypass
Ground
Terminal Wire
Tightening
Size Rating*
2
2
13.3 mm
13 3
(6 AWG)
(6 AWG)
1.8 Nm (16 lb in)
1 8 N (16 lb i )
INSTALLATION
Torque
51