Planning the Server Installation
•
Server shipping contents
Optimum Environment
When installing the server in a rack, select a location that meets the environmental
standards described in the following sections.
Information is available for optional rack adapter kits to install the server in a telco or
third-party rack. Complete instructions for using adapter kits to install the server in a
rack are included with each option kit.
•
For information about obtaining rack option kits for third-party racks, refer to the
website:
www.hp.com/servers/proliant/manage
•
For information about installing the server in a telco rack, refer to the following
website:
www.racksolutions.com/compaq
Space and Airflow Requirements
To enable servicing and adequate airflow, observe the following spatial requirements
when deciding where to install your Compaq branded or third-party rack:
•
Leave a minimum clearance of 63.5 cm (25 inches) in front of the rack.
•
Leave a minimum clearance of 76.2 cm (30 inches) in the back of the rack.
•
Leave a minimum clearance of 121.9 cm (48 inches) from the back of the rack to
the rear of another rack or row of racks.
HP servers draw in cool air through the front rack door and expel warm air through
the rear rack door. Therefore, the front and rear rack doors must be adequately
ventilated to enable ambient room air to enter the cabinet, and the rear door must be
adequately ventilated to enable the warm air to escape from the cabinet.
CAUTION: Do not block the ventilation openings.