Setup; Optional Service; Optimum Environment; Space And Airflow Requirements - HP Apollo 4200 Gen9 User Manual

Hide thumbs Also See for Apollo 4200 Gen9:
Table of Contents

Advertisement

Setup

Optional service

Delivered by experienced, certified engineers, HPE support services help you keep your servers up and
running with support packages tailored specifically for HPE ProLiant systems. HPE support services let you
integrate both hardware and software support into a single package. A number of service level options are
available to meet your business and IT needs.
HPE support services offer upgraded service levels to expand the standard product warranty with easy-to-
buy, easy-to-use support packages that will help you make the most of your server investments. Some of the
HPE support services for hardware, software or both are:
Foundation Care – Keep systems running.
6-Hour Call-to-Repair
4-Hour 24x7
Next Business Day
Proactive Care – Help prevent service incidents and get you to technical experts when there is one.
6-Hour Call-to-Repair
4-Hour 24x7
Next Business Day
Deployment service for both hardware and software
HPE Education Services – Help train your IT staff.
1
The time commitment for this repair service might vary depending on the site's geographical region. For
more service information available in your site, contact your local HPE support center.
For more information on HPE support services, see the Hewlett Packard Enterprise website.

Optimum environment

When installing the server in a rack, select a location that meets the environmental standards described in
this section.

Space and airflow requirements

To allow for servicing and adequate airflow, observe the following space and airflow requirements when
deciding where to install a rack:
Leave a minimum clearance of 63.5 cm (25 in) in front of the rack.
Leave a minimum clearance of 76.2 cm (30 in) behind the rack.
Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of another rack or
row of racks.
Hewlett Packard Enterprise servers draw in cool air through the front door and expel warm air through the
rear door. Therefore, the front and rear rack doors must be adequately ventilated to allow ambient room air to
enter the cabinet, and the rear door must be adequately ventilated to allow the warm air to escape from the
cabinet.
CAUTION:
To prevent improper cooling and damage to the equipment, do not block the ventilation openings.
When vertical space in the rack is not filled by a server or rack component, the gaps between the components
cause changes in airflow through the rack and across the servers. Cover all gaps with blanking panels to
maintain proper airflow.