Installing The Platform Into A Rack; Equipment Rack Precautions - Intel SR1325TP1 - Entry Server Platform User Manual

Entry server platform
Table of Contents

Advertisement

Platform Installations and Upgrades

Installing the Platform into a Rack

Installation instructions for the standard bracket kit and the optional rail kit are included with each
kit. These instructions can also be found at
http://support.intel.com/support/motherboards/server/chassis/SR1300/:
Intel® Server Chassis SR1200, SR1300, SR2200, and SR2300 Rail Kit Installation Guide
Intel® Server Chassis SR1200, SR1300, SR2200, and SR2300 Bracket Kit Installation Guide
NOTES
Although these documents do not refer specifically to the Intel® Entry Server
Platform SR1325TP1-E, the instructions in these documents are correct for this
platform.
The rail kit does not provide enough screws to mount the server chassis into a rack.
Your Intel Entry Server Platform SR1325TP1-E includes the extra screws necessary
to complete the installation.

Equipment Rack Precautions

CAUTION
ANCHOR THE EQUIPMENT RACK: The equipment rack must be anchored to
an unmovable support to prevent it from falling over when one or more servers are
extended in front of it on slide assemblies. The equipment rack must be installed
according to the manufacturer's instructions. You must also consider the weight of
any other device installed in the rack.
MAIN AC POWER DISCONNECT: You are responsible for installing an AC
power disconnect for the entire rack unit. This main disconnect must be readily
accessible and it must be labeled as controlling power to the entire unit, not just to the
server(s).
GROUNDING THE RACK INSTALLATION: To avoid the potential for an
electrical shock hazard, you must include a third wire safety grounding conductor
with the rack installation. If server power cords are plugged into AC outlets that are
part of the rack, then you must provide proper grounding for the rack itself. If server
power cords are plugged into wall AC outlets, the safety grounding conductor in each
power cord provides proper grounding only for the server. You must provide
additional, proper grounding for the rack and other devices installed in it.
OVERCURRENT PROTECTION: The server is designed for an AC line voltage
source with up to 20 amperes of overcurrent protection. If the power system for the
equipment rack is installed on a branch circuit with more than 20 amperes of
protection, you must provide supplemental protection for the server. If more than
one server is installed in the rack, the power source for each server must be from a
separate branch circuit.
55