Wiring and Connections

2-5

Wiring and Connections

2-5-1 AC Power Supply Unit Wiring

Caution
!
Terminal Block
CQM1-PA203
AC
input
Noise filter
neutral
terminal
Protective
earth ter-
minal
WARNING
!
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
This section provides basic information on wiring the Power Supply Unit and I/O
Units, and on connecting Peripheral Devices.
The following diagram shows the proper connection to an AC power supply. The
AC voltage should be between 100 and 240 VAC. Refer to 2-2-3 Selecting a
Power Supply Unit for details on Power Supply Unit capacity.
Remove the seal from the top of the Power Supply Unit only after wiring is com-
pleted. This seal must be removed before operating the Unit to prevent over-
heating.
The cross-sectional area of each wire must be 2 mm
Be sure that the AC power supply voltage remains within the allowed fluctuation
range of 85 to 264 VAC.
CQM1-PA216 is switchable with an input voltage range of 80 to 138 VAC or 160
to 264 VAC.
The following diagram shows the terminal blocks for the two AC Power Supply
Units.
CQM1-PA206
Use an AC
power supply
between 100
and 240 VAC.
The wire used should be at least 2 mm
the CQM1 PC as possible.
LG (
or
):
Noise filter neutral terminal. Short-circuit the LG (
terminals using the attached short-circuit bar and ground them at a resistance of
less than 100 Ω to reduce noise and prevent electric shock.
Insulating transformer
Breaker
An insulating transformer greatly
Twist the wires.
reduces the noise that may be
induced between the power line and
ground. Do not ground the secondary
side of the insulating transformer.
Use an AC
AC
power supply
input
between 100
and 240 VAC.
Noise filter
neutral
LG
terminal
Protective
GR
earth terminal
Use the 24 VDC,
0.5 A terminals
to supply power
to
DC
Input
Units.
2
. Provide the grounding point as close to
Section 2-5
2
min.
AC power supply
CQM1-PA216
Use
AC
power supply of
input
100
230 VAC.
Voltage selector
Short: 100 VAC
Open: 230 VAC
Protective
earth terminal
Use the 24 VDC,
0.5 A terminals
to supply power
to
DC
Units.
or
) terminal and GR (
an
AC
or
Input
)
25