3.3

Power Supply Unit (PSU)

3.3.1

Introduction

The PSU supplies power to the other units in the Trajexia system.
You can use three different types of Power Supply Unit with the
Trajexia system:
CJ1W-PA202
CJ1W-PA205R
CJ1W-PD025.
3.3.2

PSU Connections

Each Power Supply Unit has six terminals:
/i
Item
CJ1W-PA202
CJ1W-PA205R
A
110 - 240 VAC input
110 - 240 VAC input
B
110 - 240 VAC input
110 - 240 VAC input
1
C
Line earth
Line earth
2
D
Earth
Earth
3
E
N/C
Wdog relay contact
F
N/C
Wdog relay contact
1. The line earth terminal (C) is a noise-filtered neutral terminal.
If noise is a significant source of errors or electrical shocks are
a problem, connect the line earth terminal to the earth terminal
(D) and connect both to earth with a resistance of less than
100 Ohms.
2. To help prevent electrical shock, connect the earth terminal
(D) to earth with a resistance of less than 100 Ohms with a 14-
gauge wire or minimum cross section area of 2 mm
3. Terminals E and F for the CJ1W-PA205R are relay contacts
that close when Wdog is enabled. Refer to the BASIC Com-
mands in the Programming manual.
HARDWARE REFERENCE MANUAL
CJ1W-PD025
24 VDC input
0 V input
Line earth
Earth
N/C
N/C
2
.
fig. 18
XXXXX
G
POWER
L1
AC100
-240V
INPUT
L2/N
NC
NC
A
B
C
D
E
F
66