Devicenet Communications Card Terminal Block Wiring Procedure - Omron 3G3MV-PDRT2 User Manual

Devicenet communications units
Table of Contents

Advertisement

Setup and Wiring

DeviceNet Communications Card Terminal Block Wiring Procedure

1.Loosen the terminal screws using a thin flat-blade screwdriver.
2.Insert the wires from underneath the terminal block.
3.Tighten the terminal screws securely to a torque of 0.22 to 0.25 N·m.
Note 1. Separate the DeviceNet communications cables from the main circuit wiring and other pow-
er lines.
Note 2. Do not solder the ends of the electric wires. Doing so may cause contact failure.
Note 3. If straight crimp terminals are not used, strip the electrical wires to a length of 5.5 mm.
Note 4. Do not tighten the screws with a torque exceeding 0.5 N·m. Doing so may damage the ter-
minal block. If the screws are too loose, however, malfunctions or short circuits may result.
Strip to 5.5 mm
(if straight crimp
terminal is not used).
Strip to match the crimp terminals
Thin flat-blade screwdriver
Wire
Straight crimp
terminal or
unsoldered cable
Black Blue White Red
Chapter 3
Terminal block (TC)
3-13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3g3rv-pdrt2

Table of Contents