Appendices
●
Input Terminal Status: Register Number 002B Hex
Bit
0
Multi-function input 1 terminal S1 (1: ON)
1
Multi-function input 2 terminal S2 (1: ON)
2
Multi-function input 3 terminal S3 (1: ON)
3
Multi-function input 4 terminal S4 (1: ON)
4
Multi-function input 5 terminal S5 (1: ON)
5
Multi-function input 6 terminal S6 (1: ON)
6
Multi-function input 7 terminal S7 (1: ON)
7 to 15
Not used.
●
Inverter Status: Register Number 002C Hex
Bit
0
During Run (1: During Run)
1
Zero speed (1: zero speed)
2
Frequency agree (1: frequency agree)
3
Warning (minor fault) (1: alarm)
Frequency detection 1 (1: output frequency ≤ n095)
4
Frequency detection 2 (1: output frequency ≥ n095)
5
6
Inverter ready (1: ready)
7
UV (1: UV)
8
Baseblock (1: during baseblock)
9
Frequency reference mode (1: not communications)
10
RUN command mode (1: not communications)
11
Overtorque detection (1: over torque detection)
12
Not used.
13
Fault retry (1: fault retry)
14
Fault (1: fault)
15
Communications timeover: over 2 s without normal communications
(1: communications timeover detected)
●
Output Terminal Status: Register Number 002D Hex
Bit
0
Multi-function contact output terminal MA (1: ON)
1
Multi-function photocoupler output 1 terminal P1 (1: ON)
2
Multi-function photocoupler output 2 terminal P2 (1: ON)
3 to 15
Not used.
Inverter Status 2: Register Number 002E Hex
●
Bit
0
Frequency reference loss (1: loss)
1 to 15
Not used.