Torque Refer- Ence; Not Used; Bit - Omron 3G3MV-PDRT2 User Manual

Devicenet communications units
Table of Contents

Advertisement

Appendices
Class 64
number (hex)
Instance Attribute
00
3D
003D
00
3E
003E
00
3F
003F
00
40
0040
00
41
0041
00
42
0042
00
43
0043
00
44
0044
00
45
0045
00
46
0046
00
47
0047
00
48
0048
00
49
0049
00
4A
004A
10-46
Register
Communications error details

Bit 0

Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7 to 15
kVA setting
Control method
Frequency ref-
erence
Output fre-
quency
Output current Monitors U1-03; Percentage units: 8192 at rated
Control
method
Motor speed
Output voltage Monitors U1-06; 0.1-V units
Main circuit
DC voltage
Output power
Torque refer-
ence
Input terminal
status
Output termi-
nal status
Content
CRC error
Invalid data length

Not used.

Parity error
Overrun error
Framing error
Time-out
Not used.
Monitors U1-01; 0.01-Hz units (units set in o1-03;
with sign)
Monitors U1-02; 0.01-Hz units (units set in o1-03;
with sign)
output current
Monitors U1-04; set in A1-02
Monitors U1-05; 0.01-Hz units (units set in o1-03;
with sign)
Monitors U1-07; 1-V units
Monitors U1-08; 0.1-kW units (with sign)
Monitors U1-09; 0.1%-kW units (100% = motor's
rated torque; with sign)
Monitors U1-10; 1: ON. Bits 0 to 6 correspond to ter-
minals S1 to S7.
Monitors U1-11
Bit 0
Terminals M1 and M2; 1: ON
Bit 1
Terminals P1 and PC; 1: ON
Bit 2
Terminals P2 and PC; 1: ON
Bit 3 to
Not used.
6
Bit 7
Terminals MA and MC; 1: ON
Bit 8 to
Not used.
15
Chapter 10