Functions and System Configuration

Applicable to Various System Configurations

Remote I/O communications and message communications are available as communications func-
tions. Normal control inputs are controlled by the remote I/O communications function. When neces-
sary, the message communications function is used to monitor each Inverter. It is possible to control
the selection of either the communications control input or local control input.
Note When connecting the DeviceNet Communications Unit/Card of the Inverter, use DCA1-5C10
Thin Cables and branch them from the T-branch Tap.

System Overview

Master Unit
CS1W-DRM21(-V1)
CJ1W-DRM21
C200HW-DRM21-V1
CVM1-DRM21-V1
Remote I/O function
Output (PLC to Inverter)
Bit 7
Bit 6
Bit 5
Bit 4
Right-
0
Net.Ref. Net.Ctrl.
n
most
Left-
1
most
Right-
2
Rotational speed reference rightmost bytes
n+1
most
Left-
3
Rotational speed reference leftmost bytes
most
Input (Inverter to PLC)
1-4
Message communications function
Bit 3
Bit 2
Bit 1
Bit 0
Reset
Reverse/
Forward/
Stop
Stop
3G3MV-PDRT2 DeviceNet
Communications Unit
(For 3G3MV Inverters)
3G3RV-PDRT2
DeviceNet Communications
Card
(For 3G3RV, 3G3PV, and
3G3FV Inverters)
Note: T-branch wiring using
CMND(490)
Reading Inverter output
current
Thin Cables
Switch
Run
Reverse
Forward
Stop
Selection of either the communications control
input or local control input is possible using
Net.Ctrl./Net.Ref.
Chapter 1
3G3MV, 3G3RV, 3G3PV,
or 3G3FV Inverter
Power
supply
Motor