Procedure Before Using Fins Communications - Omron CJ1W-ETN11 Operation Manual

Sysmac cs/cj series ethernet units
Hide thumbs Also See for CJ1W-ETN11:
Table of Contents

Advertisement

Procedure Before Using FINS Communications

5-2

Procedure Before Using FINS Communications

Determine the address conversion
method for the destination IP address.
Automatic Generation
Automatically converted from
FINS node number.
Set the IP address (see note) so
that the host number's least
significant byte = the FINS node
number.
Determine the FINS UDP port number.
Is the FINS UDP port number
other than 9600?
Set the FINS UDP port number
for all Ethernet Units on the
Ethernet network to the default
of 9600.
Determine the network configuration.
Communications with PC on local network
The only Communications Units
mounted are Ethernet Units.
Routing table settings are not
required.
Create a user program for issuing
FINS messages by SEND(090),
RECV(098), and CMND(490).
82
Start
IP Address Table
Converted from table of corre-
spondences between FINS node
numbers and IP addresses.
Select the IP table address
method for the address conver-
sion method in the System Set-
up, and create an IP address
table.
In the System Setup, select
Yes
"user-defined" as the method
for specifying the FINS UDP
port number.
No
Set the FINS UDP port numbers
for all of the Ethernet Units on
the Ethernet network to the
same value.
Communications Units other than
Ethernet Units are also mounted.
Use the CX-Programmer to set
the local network table at the
CPU Unit.
Note The location of the local IP address setting depends on the type of CPU Unit
in the following way.
CS Series: Rotary switches on back of Ethernet Unit.
CJ Series: CPU Bus Unit System Setup or allocated words in the DM Area.
Combined Method
IP address table is referenced;
if IP address is not registered,
then it is converted from FINS
node number.
Select the combined method for
the address conversion method
in the System Setup, and create
an IP address table.
Communications with PC on another
network (such as Controller Link)
Use the CX-Programmer to set
the local network table and the
relay network table at the CPU
Unit.
Section 5-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-etn11Cs/cj seriesCs1w-etn01W343-e1-07