Omron 3G3MV-PDRT2 User Manual page 308

Devicenet communications units
Table of Contents

Advertisement

Appendices
Class 64
number (hex)
Instance Attribute
08
08
0808
08
09
0809
08
0E
080E
08
0F
080F
08
10
0810
08
11
0811
08
12
0812
08
13
0813
Note U3-09 to U3-20 are not supported for Asian models. Register No. 0800 Hex to 0813 Hex are
not supported for Asian models.
10-5-3 Parameter Reading and Writing
The following tables show the SYSDRIVE 3G3RV Inverter parameters and the corresponding regis-
ter numbers. Write and read the various parameters with "1" as the minimum setting unit. Negative
numbers are expressed as two's complement. If the setting unit is in hexadecimal, there is no need to
convert it.
When writing data in parameters, be sure to send an enter command to enable the written data.
Unless the enter command is transmitted, the data will not be enabled and the Inverter may not start.
10-50
Register
Connect of 9th
prior fault
Connect of
10th prior fault
Cumulative
operation time
since 5th prior
fault
Cumulative
operation time
since 6th prior
fault
Cumulative
operation time
since 7th prior
fault
Cumulative
operation time
since 8th prior
fault
Cumulative
operation time
since 9th prior
fault
Cumulative
operation time
since 10th
prior fault
Content
Monitors U3-13 (same codes as U2-01) (See note.)
Monitors U3-14 (same codes as U2-01) (See note.)
Monitors U3-15; 1-hr units (See note.)
Monitors U3-16; 1-hr units (See note.)
Monitors U3-17; 1-hr units (See note.)
Monitors U3-18; 1-hr units (See note.)
Monitors U3-19; 1-hr units (See note.)
Monitors U3-20; 1-hr units (See note.)
Chapter 10