10-7 3G3FV Register Numbers, Classes, Instances, and
Attributes
10-7-1 Inputting Control/Frequency
The Inverter's various control inputs are allocated to the registers shown in the following table. For
example, to set the frequency reference and begin operation, first set the reference value to the fre-
quency reference register "0001," and then write the run command to the Inverter's run command
register "0000."
Note 1. Set values are retained until changed by the next writing operation.
Note 2. The following registers are in RAM, so they are all cleared to zero when the Inverter's power
supply is turned OFF.
Class 64
number (hex)
Instance Attribute
00
00
0000
00
01
0001
---
---
0002 to 0006
00
07
0007
00
08
0008
00
09
0009
---
---
000A to 000F
Inverter Run Commands: Register Number 0000 Hex
Bit
0
Forward/stop (1: Forward operation)
1
Reverse/stop (1: Reverse operation)
2
Multi-function input 1
3
Multi-function input 2
4
Multi-function input 3
5
Multi-function input 4
6
Multi-function input 5
7
Multi-function input 6
8 to 15
Not used.
Inverter Outputs: Register Number 0009 Hex
Bit
0
Multi-function contact output (1: ON)
1
Multi-function output 1 (1: ON)
2
Multi-function output 2 (1: ON)
3 to 15
Not used.
10-84
Register
Function
Inverter run command (Refer to table below.)
Frequency reference
Not used.
Multi-function analog
output 1 (See note 2.)
Multi-function analog
output 2 (See note 2.)
Inverter output (See
note 3.)
Not used.
Content
Content
Content
Sets frequency reference value. (See note
1.)
---
+11 V = 02D6 hex
+11 V = 02D6 hex
(Refer to table below.)
---
Chapter 10