Remote I/O Functions

SYSDRIVE 3G3RV/3G3PV/3G3FV Inverters

Byte number
Wd n
Right-
0
Multi-
most
function
input 6
Left-
1
Multi-
most
function
output 2
Wd n+1
Right-
2
Frequency reference, rightmost byte
most
Left-
3
Frequency reference, leftmost byte
most
Wd n+2
Right-
4
Torque reference/torque limit, rightmost byte
most
Left-
5
Torque reference/torque limit, leftmost byte
most
Wd n+3
Right-
6
Torque compensation bias, rightmost byte
most
Left-
7
Torque compensation bias, leftmost byte
most
Inputs (Inverter to PLC)
Byte number
Wd m
Right-
0
Fault
most
Left-
1
P lock
most
comple-
tion (See
note 4.)
Wd m+1 Right-
2
Output frequency monitor, rightmost byte
most
Left-
3
Output frequency monitor, leftmost byte
most
Wd m+2 Right-
4
Torque reference monitor, rightmost byte
most
Left-
5
Torque reference monitor, leftmost byte
most
Wd m+3 Right-
6
Output current monitor, rightmost byte
most
Left-
7
Output current monitor, leftmost byte
most
Note 1. A shaded box indicates that the bit is not used.
Note 2. Control remote I/O inputs and outputs are paired. When using control remote I/O, be sure
to set them together.
Note 3. Control remote I/O objects do not conform to the AC/DC drive profile, but are specially set
for this product.
Note 4. The P lock function (position lock or zero-servo function) is valid only for a 3G3FV Inverter
operating with flux vector control. This bit is not used with other Inverters or control modes.
Bit 7
Bit 6
Bit 5
Multi-
Multi-
function
function
input5
input4
Multi-
Multi-
function
function
output 1
contact
output
Bit 7
Bit 6
Bit 5
Alarm
Inverter
(minor
ready
fault)
Multi-
function
output 2
Bit 4
Bit 3
Bit 2
Multi-
Multi-
Multi-
function
function
function
input3
input2
input1
Instance ID: 151 Decimal (97 Hex)
Bit 4
Bit 3
Bit 2
At refer-
During
During
ence
reset
reverse
input
run
Multi-
Multi-
Local/re
function
function
mote
output 1
contact
output
Chapter 5
Bit 1
Bit 0
Reverse/
For-
stop
ward/sto
p
Fault
External
reset
fault
input
Bit 1
Bit 0
Zero
During
speed
run
Power
Opera-
interrup-
tion fault
tion
recovery
5-21