F020
Preset Speed 3
Preset Speed 3
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0011 and is
identified as Preset Speed 3. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 4
Preset Speed 4
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0100 and is
identified as Preset Speed 4. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 5
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0101 and is
identified as Preset Speed 5. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 6
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0110 and is
identified as Preset Speed 6. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
Preset Speed 7
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0111 and is
identified as Preset Speed 7. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
this parameter).
84
efesotomasyon.com -Toshiba inverter,drive,servo,plc
F018
for more information on
F018
for more information on
F018
for more information on
F018
for more information on
F018
for more information on
F024
Direct Access Number — F020
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F021
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F022
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F023
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
Direct Access Number — F024
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — Lower Limit (F013)
Maximum — Upper Limit (F012)
Units — Hz
G9 ASD Installation and Operation Manual