Figure 4. The Grounding Capacitor
Switch is used on typeforms 230-volt
0.5 HP to 10 HP and the 25 and 30 HP/
460-volt 1.0 HP to250 HP.
The value may be set to Maximum
(default setting) or to Zero by pushing
or pulling the switch actuator,
respectively.
Figure 5. The Grounding Capacitor
Switch is used on typeforms 230-volt
15 HP to 20 HP and the 40 HP to
60 HP/460-volt 30 HP to 100 HP.
The value may be set to Large (default
setting) or Small by pushing or pulling
the switch actuator, respectively.
Figure 6. The Grounding Capacitor
Bar is used on typeforms 230-volt 75
HP and the 100 HP/460-volt 125 HP
and the 150 HP.
The value may be set to Large or
Small (default setting) by connecting
or disconnecting the switching bar,
respectively.
Figure 7. The Grounding Capacitor
Screw is used on typeforms 460-volt
175 HP and above.
The value may be set to Large or
Small (default setting) by placing the
screw in the A position or by placing
the screw in the B position,
respectively.
G9 ASD Installation and Operation Manual