Startup Wizard Parameter Requirements
The Startup Wizard queries the user for information on the I/O signal parameters, control, and the EOI
display settings of the ASD. The ASD may also be setup by directly accessing each of the startup settings
via the
Program
menu or the associated Direct Access Numbers (see the section titled
Parameter Information on pg.
Upon initial system power up, the Startup Wizard starts automatically. It may also be run from the
Program
menu after startup, if required. The user is queried to either (1) Run Now, (2) Run Next Time, or
(3) Manually Configure the ASD.
Select Run Now to start the Startup Wizard. The wizard will assist the user with the configuration of the
ASD using the user-input screens below.
Select Run Next Time to return to the
the next power up.
Select Manually Configure to go to the Finish box. Click Finish to return the system to the Frequency
Command screen.
Voltage and Frequency Rating of the Motor
Motors are designed and manufactured to be operated within a specific voltage and frequency range. The
voltage and frequency specifications for a given motor may be found on the nameplate of the motor.
Highlight and click the voltage and frequency of the motor being used.
Upper-Limit Frequency
This parameter sets the highest frequency that the ASD will accept as a frequency command or frequency
setpoint. The ASD may output frequencies higher than the Upper-Limit Frequency (but, lower than the
Maximum Frequency) when operating in the PID Control mode, Torque Control mode, or the Vector
Control modes (sensorless or feedback).
Lower-Limit Frequency
This parameter sets the lowest frequency that the ASD will accept as a frequency command or frequency
setpoint. The ASD will output frequencies lower than the Lower-Limit Frequency when accelerating to
the lower-limit or decelerating to a stop. Frequencies below the Lower-Limit may be output when
operating in the PID Control mode, Torque Control mode, or the Vector Control modes (sensorless or
feedback).
Automatic Acceleration/Deceleration
When Automatic ACC/DEC is chosen, the ASD adjusts the acceleration and deceleration rates according
to the applied load. The minimum accel/decel time may be set using F508. The motor and the load must
be connected prior to selecting Automatic Accel/Decel.
Select Manual to allow the settings of
acceleration and deceleration times range from 12.5% to 800% of the programmed values for the active
acceleration time.
Select Automatic ACC Only to allow for the acceleration rate to be controlled automatically only.
Acceleration Time
This parameter specifies the time in seconds for the output of the ASD to go from 0.0 Hz to the Maximum
Frequency for the 1 Acceleration profile. The Accel/Decel Pattern may be set using F502.
G9 ASD Installation and Operation Manual
76).
Program
menu. The system will default to the Startup Wizard on
F009
and
F010
to control the accel/decel, respectively. The