efesotomasyon.com -Toshiba inverter,drive,servo,plc
F690
MON 1 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.
Set the assigned function of parameter
to a zero output.
See parameter
F672
for more information on this setting.
MON 2 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON2 output
terminal.
See parameter
F674
for more information on this setting.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
MON 2 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
MON 2 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON2 terminal.
Set the assigned function of parameter
to a zero output.
See parameter
F674
for more information on this setting.
Parameter Write Lockout
Program Utilities Prohibition
This parameter Enables/Disables the Run and Stop keys.
Settings:
0 — Enabled
1 — Disabled
196
F672
to zero and then set this parameter
F674
to zero and then set this parameter
F700
Direct Access Number — F690
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F691
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes
Direct Access Number — F692
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
Direct Access Number — F693
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F700
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
G9 ASD Installation and Operation Manual