Toshiba G9 Installation And Operation Manual page 175

Asd
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
F504
Acc/Dec Pattern 1 – 4
Program Special  Acc/Dec Special
Four Acceleration times and four Deceleration times may be set up and run
individually. Accel/Decel Time 1 – 4 may be selected using this parameter
setting or switched via threshold frequencies, or by discrete input terminal.
This parameter is used to select one of the four configured accel/decel profiles
to be used.
Settings:
1 — Acc/Dec 1
2 — Acc/Dec 2
3 — Acc/Dec 3
4 — Acc/Dec 4
Each Accel/Decel selection is comprised of an Acceleration Time,
Deceleration Time, and a Pattern selection. Selection 1, 2, and 3 have a
Switching Frequency setting. The Switching Frequency is used as a threshold
frequency that, once reached, the ASD switches to the next Acc/Dec selection.
Switching Frequency settings are used during acceleration and deceleration. A
switching frequency setting is not required for Acc/Dec 4.
Acc/Dec 1 is set up using parameters
(Pattern), and
F505
(Switching Frequency).
Acc/Dec 2 is set up using parameters
(Pattern), and
F513
(Switching Frequency).
Acc/Dec 3 is set up using parameters
(Pattern), and
F517
(Switching Frequency).
Acc/Dec 4 is set up using parameters
F516
(Pattern).
This parameter (F504) is used to manually select Acc/Dec 1 – 4.
To switch using the Terminal Board, assign the functions Acc/Dec Switching
1 and Acc/Dec Switching 2 to two discrete input terminals. Activation
combinations of the two terminals result in the Acc/Dec 1 – 4 selections as
shown in
Table
4.
Figure 30
shows the setup requirements and the resulting output frequency
response when using Switching Frequency settings to control the Acc/Dec
response of the ASD output.
While operating using S-Pattern 1 the system performance may be further
enhanced by the adjustment of parameters
for upper and lower Acc/Dec limit adjustments. These settings are used to
extend or shorten the upper or lower Acc/Dec curve.
Note:
If operating from the Local mode, press Esc from the Frequency
Command screen to access this parameter.
Accel/Decel Switching Frequency 1
Program Special  Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel 1 profile to the Accel 2 profile during a multiple-acceleration
profile configuration.
G9 ASD Installation and Operation Manual
F009
(Acc Time),
F010
(Dec Time),
F500
(Acc Time),
F501
(Dec Time),
F510
(Acc Time),
F511
(Dec Time),
F514
(Acc Time), and
F515
(Dec Time),
F506
– F509. These settings provide
Direct Access Number — F504
Parameter Type — Selection List
Factory Default — 1
Changeable During Run — Yes
Table 4
.
Using combinations of discrete terminal
activations Accel/Decel profiles 1–4 may
be selected.
Acc/Dec Switching Truth
A/D SW 1 A/D SW 2 Acc/Dec # Out
0
0
0
1
1
0
1
1
1 = Discrete terminal activation.
F502
F503
Figure 30
. Using Acc/Dec Switching.
F512
1 — Accel time 1
(F009
setting)
2 — Accel time 2
(F500
setting)
3 — Accel time 3
(F510
setting)
4 — Accel time 4
(F514
setting)
5 — Decel time 4
(F515
setting)
6 — Decel time 3
(F511
setting)
7 — Decel time 2
(F501
setting)
8 — Decel time 1
(F510
setting)
Direct Access Number — F505
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F505
1
2
3
4
167

Advertisement

Table of Contents
loading

Table of Contents